5 Technical Specifications
5.1 Operating Environment
Parameter
Range
Comments
Ambient Operating Temperature
-40 to 85
°
C
Ambient Temperature as
measured from a 30 cm radius
surrounding the center of the
RS910 enclosure.
Ambient Storage Temperature
-40 to 85
°
C
Ambient Relative Humidity
5% to 95%
Non-condensing
Table 4 - Operating Environment
5.2 Power Supply Specifications
Power Supply Type
Minimum
Input
Maximum
Input
Fuse
Rating
Isolation
Maximum Power
Consumption
12 – 24 VDC
10 VDC
36 VDC
3.15 (T)
1.5 kV DC
24 VDC
18 VDC
36 VDC
3.15 (T)
1.5 kV DC
48 VDC
36 VDC
72 VDC
3.15 (T)
1.5 kV DC
HI (125/250 VDC) 1
HI (110/230 VAC) 1
88 VDC
85 VAC
300 VDC
265 VAC
3.15 (T)
4 kV AC 5.5
kV DC
10W
Table 5 - Power Supply Specifications
NOTES:
1.
This is the same power supply for both AC and DC.
2.
(F) Denotes fast-acting fuse, (T) denotes time-delay fuse.
3.
For continued protection against risk of fire, replace only with same type and rating of fuse.
5.3 Failsafe Relay Specifications
Load Circuit
SELV
TNV-2
MAX operating Voltage
30VDC
30 VAC
80VDC
MAX operating Current
1A
0.5A
0.3A
Isolation (between coil and contacts)
1800 V
rms
Table 6 - Failsafe Relay Specifications