2. Serial Protocols
ROS® v3.11User Guide
64
RMC30
Default: 1
The port number as seen on the front plate silkscreen of the switch.
Pack Char
Synopsis: 0 to 255 or { Off }
Default: Off
The character that can be used to force forwarding of accumulated data to the network.
If a packetization character is not configured, accumulated data will be forwarded based
upon the packetization timeout parameter.
Pack Timer
Synopsis: 3 to 1000
Default: 10 ms
The delay from the last received character until when data is forwarded.
Flow Control
Synopsis: { None, XON/XOFF }
Default: None
The Flowcontrol setting for serial port.
Loc Port
Synopsis: 1024 to 65535
Default: 62001
The local IP port to use when listening for an incoming connection or UDP data.
Rem Port
Synopsis: 1 to 65535
Default: 62000
The remote TCP port to use when placing an outgoing connection.
IP Address
Synopsis: ###.###.###.### where ### ranges from 0 to 255 or
{ <EMTY STRING> }
Default:
The permanent master's IP address. Empty string represents management IP address of
this device.
Link Stats
Synopsis: { Disabled, Enabled }
Default: Enabled
Enables link statistics collection for this protocol.
Dyn Pack Char
Synopsis: 0 to 255 or { Off }
Default: Off
The character that can be used to force the forwarding of accumulated data to the
network for connection to a dynamic master. If a packetization character is not configured,
accumulated data will be forwarded based upon the packetization timeout parameter.
Dyn Pack Timer
Synopsis: 3 to 1000
Default: 10 ms