As specified by Rs485 standard, Rs485 Bus is of
half-duplexed data transmission cables with chara-
cteristic impedance as 120
Ω
. The maximum load
capacity is 32 unit loads (including main controller
and controlled equipment.)
Transmission distances of Rs485 Bus
When user selects the 0.56mm(24AWG)twist-
ed pair wires as data transmission cable, the maxi-
mum theoretical transmitting distance are as foll-
ows:
If user selects thinner cables, or installs the PTZ
in an environment with strong electromagnetic
interference, or connects lots of equipment to the
Rs485 Bus, the maximum transmitting distance w-
ill be decreased. To increase the maximum transm-
itting distance, do the contrary.
Connection and termination resistor
The Rs485 standards require a daisy-chain Conn-
ection between the equipment. There must be ter-
mination resistors with 120
Ω
(as the picture 9-2.1).
Please refer to picture 9-2.2 for simple connection.
“
D
”
should not exceed 7m.
Characteristics of Rs485 Bus
9. 4 Rs485 Bus Basic Knowledge
120
Ω
1# 2# 3# 4# 32#
Picture 9-4.1
120
Ω
120
Ω
1# 2# 3# 4# 32#
D
A+
B-
A+
B-
Picture 9-4.2
120
Ω
2400BPS
4800BPS
9600BPS
1800m
1200m
800m
Baud rate
Max distance
19200BPS
600m
Picture9-4.3
Ø
The connection of 120
Ω
termination resistor:
Connection mode for 120 resistance of equipment
terminal. Setting connection of terminal resistance
120 in the base cover. (Refer to Picture 9-4.3):
Default of factory (No.8 digit of SW2 is set “OFF”
on code switch)No.8 digit of SW2 is set “ON” on
code switch if needed to connect 120 resistance.
Ω