5.9. Convection air duct
The cross sections for the air inlet opening [14] and
the air outlet opening [15] should be 700 cm² each,
however, at least 350 cm².
At least 200 cm² of the air inlet and air outlet opening
must not be sealable.
No combustible construction materials, e.g. wood
ceiling, and no fitted furniture must be located within
an area of 30 cm next to and 50 cm above the air out-
let openings [15].
5.10. Ceiling above fire insert
If the fire place cowl gap above the fire insert contin-
ues until the room ceiling [17] it has to be protected, if:
- it consists of combustible components
- it is a load-bearing element.
The protection consists of a thermal insulation layer
with a thickness of 12 cm [9] and a load-bearing, min-
eral roofing with a thickness of 2 cm [19]
5.11. Floor in front of the fire insert
The floor in front of the fire insert must consist of non-
combustible material. Minimum dimensions of this
non-combustible surface:
to the front:
- at least 40 cm.
to both sides:
- at least 40 cm.
5.12. Fire protection in the radiation area
A minimum distance of 80 cm from the top and from
both sides must be provided between the furnace
opening and combustible components. In case of ar-
rangement of a radiation protection ventilated from
both sides a distance of 40 cm is sufficient.
1
2
c
m
Содержание JUPITER 510 HK
Страница 1: ...SMART LINE ECO LINE INSTALLATION GUIDE...
Страница 2: ......
Страница 26: ...SMART LINE ECO LINE Installation Guide 26 8 Mars 570 K with ceramic flue example with KMS system...
Страница 34: ...SMART LINE ECO LINE Installation Guide 34 Notes...
Страница 35: ...SMART LINE ECO LINE Installation Guide 35...
Страница 36: ...www ruegg cheminee com 89 90 00454 ma_smart line_en_rev2_07 2013...