11.4. Current value table
Register
address
Protocol
address
Parameter name
Value range
Data type Authority
30001
0
Unit identification
10000
integer
R
30002
1
Room temperature
Temp in 1/10 ° - 500 to 1000
integer
R
30003
2
Supply-air temperature
Temp in 1/10 ° - 500 to 1000
integer
R
30004
3
Outlet-air temperature
Temp in 1/10 ° - 500 to 1000
integer
R
30005
4
Exhaust-air temperature
Temp in 1/10 ° - 500 to 1000
integer
R
30006
5
Outdoor-air temperature
Temp in 1/10 ° - 500 to 1000
integer
R
30007
6
Pressure-difference, filter 1
0 - 1000 Pa
integer
R
30008
7
Pressure-difference, filter 2
0 - 1000 Pa
integer
R
30009
8
Soiling indicator 1
0 - 100%
integer
R
30010
9
Soiling indicator 2
0 - 100%
integer
R
30011
10
Program version
0 - 100
integer
R
30012
11
Operating hours
(0 - 32767) *10
integer
R
30013
12
Number of filter changes
0 - 32767
integer
R
30014
13
Inputs
See Table below
integer
R
30015
14
Outputs
See Table below
integer
R
30016
15
Volumetric flow supply air in m³/h
integer
R
30017
16
Volumetric flow extract air in m³/h
integer
R
30018
17
Reserved
integer
R
30019
18
Reserved
integer
R
30020
19
Used by system
integer
R
30021
20
Used by system
integer
R
30022
21
Valve setting, heating valve
0 - 100%
integer
R
30023
22
Valve setting, cooling valve
0 - 100%
integer
R
30024
23
Actual sensor value
0-2000 ppm / 0-100 % Humidity
integer
R
30025
24
Error number
See Table below
integer
R
30026
25
Reserved
integer
R
30027
26
Pressure supply air analogue input 2
integer
R
30028
27
Pressure extract air analogue input 3
integer
R
30029
28
Reserved
integer
R
30030
29
Reserved
integer
R