44
English
Tel. +49 7930 9211-0 Fax +49 7930 9211-150
Current value table, protocol addresses 14 (outputs)
Current value table, protocol addresses 24 (error numbers)
Current value table, protocol addresses 13 (inputs)
Bit 0
Reserved
Bit 1
Reserved
Bit 2
1 = Cooling requirement
Bit 3
1 = Bypass open
Bit 4
1 = Bypass closed
Bit 5
1 = Heating valve open
Bit 6
1 = Heating valve closed
Bit 7
1 = Heating pump on
Bit 8
1 = Unit defective
Bit 9
1 = Damper closed
Bit 10
1 = Damper open
Bit 11
1 = Cooling valve open
Bit 12
1 = Cooling valve closed
Bit 13
1 = E-heating on
Bit 14
1 = Enable frequency converter
Bit 15
Reserved
Value
0
No error
1
Supply-air temperature sensor defective
2
Room-air temperature sensor defective
3
Outlet-air temperature sensor defective
4 Exhaust-air temperature sensor defective
5
Outdoor-air temperature sensor defective
6
Damper position
7
Frost protection triggered
8
Safety thermostat triggered
9
Thermal switch for ventilator triggered
10
Frequency converter defective
11 Reserved
12
Not enabled
13
Cooling plant defective
14
Fire detector
15 Reserved
16 Reserved
17
Supply-air temperature too low
18
Supply-air temperature too hot
19 Reserved
20
Heat exchanger
Bit 0
1 = Enable_signal_external
Bit 1
1 = Frequency converter ready
Fan motor electronic ok
Bit 2
1 = Thermal switch, fan
Bit 3
1 = Frost protection OK
Bit 4
1 = Motion detector
Bit 5
1 = Fire detector ok
Bit 6
Reserved
Bit 7
Reserved
Bit 8
Reserved