16. Appendix
16.1. List of parameters
The following table lists all of the parameters that are displayed on the control unit, some of which
may be changed. Section 9.3.4. „Parameter settings menu“ gives full instructions on operating and
setting the corresponding parameters.
No.
Consequence
Range of values
Factory setting
P 1
Mini.set-point temp. that can be set on the control unit
16 °C ... 20 °C
16 °C
P 2
Max. set-point temp. that can be set on the control unit
20 °C … 30 °C
22 °C
P 3
External release
AUTOMATED
ACKNOWLEDGED
AUTOMATED
P 4
I - component
5 ... 20
10
P 5
P - component
5 ... 20
10
P 6
Temp. correction of the ambient temp. sensor on the control unit -5 °C ... 5 °C
0
P 7
Address
1 - 247
1
P 8
Baud rate
2400 / 4800 / 9600 / 14400
9600
P 9
Fan calibration supply air
800 - 1200
1.000
P 10
Fan calibration extract air
800 - 1200
1.000
P 13
Type
S / PV / P
S
P 14
Sensor type
CO2 / VOC / EXT.CTRL. / HUMIDITY
Units / Model
P 15
Minimum ventilation supply air
P 16
Minimum ventilation extract air
P 17
Basic ventilation supply air
P 18
Basic ventilation extract air
P 19
Intermittent ventilation supply air
P 28
Intermittent ventilation extract air
P 20
Air quality
CO2 / VOC / r.F
1400 ppm / 45 %
P 21
Type of regulation
SUP.AIR TEMP.CON / ETA TEMP.CTRL /
ROOMTEMP.CONTROL
SUP.AIR TEMP.CON
P 22
Selection of heating system
HEATING / COOLING / HEATING-COOLING
DIRECT EVAPORATO
HEATING
P 23
Sensor measuring range min.
0 ppm
P 24
Sensor measuring range max.
2000 ppm
P 25
Supply air filter
0 - 500 Pa
100 Pa
P 26
Extract air filter
0 - 500 Pa
100 Pa
P 27
Calibrate filter
P 29
ETAK TYPE
HW / HE / VW / VE / FW / FE
P 30
Extended running time
1 - 60 mins
5 MIN.