P 26 Extract air filter pressure loss
Setting for pressure loss at the supply air filter before the filter is clogged or 100% clogging is rea
-
ched. The current level of clogging can be seen on the status display. The factory setting is 100 Pa.
You might have to optimize the settings if a different type of filter is used.
P 27 Calibrate filter
Calibrating the pressure loss at the unclogged filter.
The calibrated value corresponds to 0% clogging.
For the filters to be calibrated the whole ventilation system has to be set up and
adjusted.
Pushing the B (▲) button opens automatically the calibration mode. Display flashes
„FILTER CALIBRATION“ After calibration, the display shows „COMPLETED“.
P 25 Supply air filter pressure loss
Setting for pressure loss at the supply air filter before the filter is clogged or 100% clogging is rea
-
ched. The current level of clogging can be seen on the status display. The factory setting is 100 Pa.
You might have to optimize the settings if a different type of filter is used.
P 30 Follow-up time
This parameter sets the stop delay of the motion detector input. The device runs for intermittent
ventilation with the adjusted time according to parameter 19 and 28.
9.5. Menu parameter level
Parameter values, see table 16.1. List of parameters.
You move to the parameter settings menu by pressing the ON/OFF button, which must be held down
for approx. 9 seconds. The display then changes to „P 1 MIN-VALUE“. The individual menu points
can be called up with buttons A (▲ and ▼) on the control unit. The values can be changed with but
-
tons B (▲ and ▼). Press the „Mode button“ (M) to go back to the starting functions.
P 1 Minimum set-point value
Parameter P 1 gives the minimum set-point temperature that can be set on the control unit. Values
between 16 °C and 20 °C can be selected. The default setting is 16 °C.
P 2 Maximum set-point value
Parameter P 2 gives the maximum set-point temperature that can be set on the control unit. Values
between 20 °C and 30 °C can be selected. The default setting is 22 °C.
P 3 Enable
Switching the unit on and off with an external contact
The unit must be switched on at the control unit.
Contact open. The unit is switched off.
Contact closed. The unit is switched on / ready for operation.
The unit can only be switched on if the contact is closed. If the contact is open, the
display will show „NOT ENABLE“. The contact should be closed and then acknow
-
ledged with button B (▲).
The default mode is AUTOMATIC.
P26 EXH.AIR FILT
100 PA
P27
CALIBRATE FILTER
P27
COMPLETED
P30 RUN-ON TIME
5 MIN.
P25 SUP.AIR FILT
100 PA
Constant 9 sec
hold down
P1 MIN-VALUE
16,0°
P2 MAX-VALUE
24,0°
P3 ENABLE
AUTOMATED
P3 ENABLE
AUTOMATED
P3 ENABLE
ACKNOWLEDGED