Installation, operating and maintenance instructions

15.  LIFETIME AND DISPOSAL

15.2.  Decommissioning and disposal

When disassembling, parts under voltage are exposed, which can lead to electric shock when touched. 

Before dismantling, disconnect the fan from all poles of the mains and secure against being switched 

on again!

Parts and components of the device that have reached their lifetime, e.g. due to wear, corrosion, mechanical stress, 
fatigue and/or all other, not directly recognizable effects, must be disposed of professionally and properly after disas-
sembly in accordance with national and international laws and regulations. The same applies to excipients in use such 
as oils and fats or other substances. The conscious or unconscious reuse of used components such as e.g. impellers, 
rolling bearings, motors. etc. can lead to a risk to persons, the environment as well as machinery and equipment. The 
applicable local operating regulations must be observed and applied.

15.1.  Product life

15.3.  Spare parts (motor + impeller)

Only original spare parts may be used.
The repair may only be carried out by personnel trained and authorized.

The motors are equipped with maintenance-free, permanently lubricated ball bearings. Under normal operating condi-
tions, the expected lifetime is about 30,000 operating hours.
The information given here depends strongly on the respective field of application as well as the environmental condi-
tions. We recommend replacing these fans after reaching about 30,000 operating hours or 5 years.

Fault

Possible cause

Remedy methods

 

Fan does not start  

No power supply

 

Check mains supply / connections

 

Impeller does not rotate freely

 

Check the causes and, if possible, remove 

them. If not possible, contact the supplier.

 

Engine overhea-

ted / temperature 

protection is swit-

ched on

 

Fault of the ball bearings

 

Contact the supplier

 

Too high operating temperature

 

Observe the data on the nameplate

 

Air flow is too low, motor cannot cool 

down

 

See fault „Low air flow“

 

Abnormal noises / 

vibrations

 

Dirt deposits on the impeller

 

See chapter maintenance and cleaning

 

Imbalance of the impeller

 

Contact the supplier

 

Connection with intake or exhaust pipe 

causes vibrations and oscillations

 

Install fan with vibration dampers

 

Fixing screws released

 

Tighten screws

 

Fault of the ball bearings

 

Contact the supplier

 

Loose impeller blade

 

Contact the supplier

 

Low airflow

 

Impeller runs in the wrong direction (wrong 

air transport direction)

 

Note the marking on the device / namepla-

te. Check electrical connections

 

High pressure losses in the system

 

Improve piping configuration or select a 

more powerful fan

 

Back flow shutter flaps not at all or only 

partially open

 

Check the backflow flap on site

 

Inlet clogged

 

Remove blockage

 

Speed control incorrectly set / incorrectly 

connected

 

Check settings / switching unit and possibly 

adjust / connect

16. TROUBLESHOOTING

Содержание DVN***D.F4 Series

Страница 1: ...OPEAN PARLIAMENT 9 10 TRANSPORT AND STORAGE 10 11 ASSEMBLY 10 12 ELECTRICAL CONNECTION 13 13 COMMISSIONING 15 14 MAINTENANCE AND CLEANING 16 15 LIFETIME AND DISPOSAL 18 16 TROUBLESHOOTING 18 ruck Vent...

Страница 2: ...bleshooting of the product The product has been manufactured according to the accepted rules of current technology There is however still a danger of personal injury or damage to equipment if the foll...

Страница 3: ...re 3 GENERAL SAFETY INSTRUCTIONS Planners plant engineers and operators are responsible for ensuring that the product is installed and operated correc tly Use our devices only in perfect technical con...

Страница 4: ...tructions before the steps whenever there is a danger of personal injury or damage to the equipment The measures described to avoid these hazards must be observed Safety instructions are set out as fo...

Страница 5: ...Before performing any work on conductive parts al ways disconnect the unit completely from the electri city supply and make sure that it cannot be switched back on again Never reach into the impeller...

Страница 6: ...ed to operate the setting mechanisms of the components or parts under the provision that the system is used as intended In an emergency or if there is a fault or other irregularities switch the equipm...

Страница 7: ...P 2015 Catalog item number Test date CE mark Grounding Series perm temperature time in smoke extraction perm temperature in continuous operation DVN D F4 400 C 120 min 20 C bis 200 C DVNI D F4 400 C 1...

Страница 8: ...8 5 50 200 91 86 146916 163 0 DVNI 710 D6 F4 30 144626 400V 3 Y 50 2768 6 9 50 200 83 143654 144615 534 467 363 341 484 556 245 4x 9 213 6x M6x15 144616 534 467 363 341 484 556 245 4x 9 213 6x M6x15 1...

Страница 9: ...etermining the fan ener gy efficiency such as ducts that are not described in the measure ment category and not supplied with the fan Units Model ID number see nameplate ruck Ventilatoren GmbH Local D...

Страница 10: ...ion If moisture has penetrated into the original packaging remove it immediately Storage temperature between 5 C and 40 C Avoid severe temperature fluctuations If the product has been in storage for m...

Страница 11: ...e nozzle plate 4 with hexagonal screws and sealing washers 5 6 on roof socket DSF If required it is possible to install further accessories at this point see 11 3 Installation examples with accesso ri...

Страница 12: ...26383 DVNI D F4 EN Installation operating and maintenance instructions 11 3 Installation examples DSF DAS DAF Tube Roof fan DSF Tube DSF DAS DAF Tube Roof fan DVK DSF DVK DAS DAF Tube Roof fan DSF DVK...

Страница 13: ...g between the unit and the duct system Check all protective measures after the electrical connection work earthing resistance etc Motor current and motor power must not exceed the values stated on the...

Страница 14: ...e time For the delta circuit the shorting blades are connecting U1 with W2 V1 with U2 and W1 with V2 see Img Never connect both jumpers at the same time If in spite of the correct connection to the ma...

Страница 15: ...lectric motors heat up Under certain circumstances excessively high ambient or fluid temperatu res heavy contamination etc the motor temperature may exceed the safety limit of the electrically isolate...

Страница 16: ...6 months Check impeller rotation direction yearly Check flexible connections for leaks yearly Check impeller for imbalance yearly Check protective device for function yearly Motor Check externally for...

Страница 17: ...all the threaded studs 3 and screw them out completely Lubricate a threaded pin and screw it into the disassembly hole 4 2 Tighten the threaded pin until the clamping bush 1 is released from the hub...

Страница 18: ...given here depends strongly on the respective field of application as well as the environmental condi tions We recommend replacing these fans after reaching about 30 000 operating hours or 5 years Fa...

Страница 19: ...19 EN Notes www ruck eu...

Страница 20: ...nt 25 02 2019 mdnif_pb_05_en We reserve the right to make changes Language English ruck Ventilatoren GmbH Max Planck Str 5 D 97944 Boxberg Windischbuch Tel 49 0 7930 9211 300 Fax 49 0 7930 9211 166 in...

Отзывы: