background image

14

0.245 kg

 

A4

Do not scale drawing

Protection Mark according to ISO16016

  mm

mm

General tolerances DIN ISO 2768-mK

1:2

ruck Ventilatoren

Max-Planck-Str. 5

D-97944 Boxberg Daniel Andree

12.10.2017

Klemmkasten_extern

 

 

Intern

0.245 kg

 

A4

Do not scale drawing

Protection Mark according to ISO16016

  mm

mm

General tolerances DIN ISO 2768-mK

1:2

ruck Ventilatoren

Max-Planck-Str. 5

D-97944 Boxberg Daniel Andree

12.10.2017

Klemmkasten_extern

 

 

Intern

0.001 kg

Material <nicht festgelegt>

A4

Do not scale drawing

Protection Mark according to ISO16016

 mm

mm

General tolerances DIN ISO 2768-mK

2:1

ruck Ventilatoren

Max-Planck-Str. 5

D-97944 Boxberg Daniel Andree

12.10.2017

140777

 

 

Intern

0.001 kg

Material <nicht festgelegt>

A4

Do not scale drawing

Protection Mark according to ISO16016

 mm

mm

General tolerances DIN ISO 2768-mK

2:1

ruck Ventilatoren

Max-Planck-Str. 5

D-97944 Boxberg Daniel Andree

12.10.2017

140777

 

 

Intern

K

W

W

1

Drehstrommotor

= kundenseitiger Anschluss 

K

= werkseitiger Anschluss 

W

1

= Zuleitung Motor 

W

K

|  DVNI...D.F4

EN

Installation, operating and maintenance instructions

 

Star circuit

 

Delta circuit

12.4.  Star circuit / Delta circuit

For the star circuit, the terminals U2, V2 and W2 are 
connected through the shorting blades (see Img.).

Never connect both jumpers at the same time!

For the delta circuit, the shorting blades are connecting 
U1 with W2, V1 with U2 and W1 with V2 (see Img.).

Never connect both jumpers at the same time!

If, in spite of the correct connection to the mains or to the frequency converter, the devices turn contrary 

to the given direction of rotation, this must be corrected. For this purpose two phases can be interch-

anged at the terminal block (e.g. L1 with L2 or L2 with L3). Afterwards the direction of rotation is to be 

checked again.
For the electrical connection, for the setting of the motor protection switch or for the parameterization 

of a frequency inverter, only the technical data on the nameplate of the fan are relevant. These may differ 

from the technical data of the motor.

The star circuit must be used if the motor is to be ope-
rated directly on the 3-phase supply network with a 
line voltage of 400V.

The star circuit is also to be used when controlling via a 
frequency inverter with 400V output voltage (usually a 
frequency converter with 3-phase 400V mains connec-
tion).

The delta circuit must be used if the motor is to be ope-
rated directly on the 3-phase supply network with a 
line voltage of 230V.

The delta circuit is also to be used when controlling 
via a frequency inverter with 230V output voltage (in 
general frequency converter with 1-phase 230V mains 
connection).

12.3.  Cable connection

factory connection

customer-side connection

Three-phase motor

Содержание DVN***D.F4 Series

Страница 1: ...OPEAN PARLIAMENT 9 10 TRANSPORT AND STORAGE 10 11 ASSEMBLY 10 12 ELECTRICAL CONNECTION 13 13 COMMISSIONING 15 14 MAINTENANCE AND CLEANING 16 15 LIFETIME AND DISPOSAL 18 16 TROUBLESHOOTING 18 ruck Vent...

Страница 2: ...bleshooting of the product The product has been manufactured according to the accepted rules of current technology There is however still a danger of personal injury or damage to equipment if the foll...

Страница 3: ...re 3 GENERAL SAFETY INSTRUCTIONS Planners plant engineers and operators are responsible for ensuring that the product is installed and operated correc tly Use our devices only in perfect technical con...

Страница 4: ...tructions before the steps whenever there is a danger of personal injury or damage to the equipment The measures described to avoid these hazards must be observed Safety instructions are set out as fo...

Страница 5: ...Before performing any work on conductive parts al ways disconnect the unit completely from the electri city supply and make sure that it cannot be switched back on again Never reach into the impeller...

Страница 6: ...ed to operate the setting mechanisms of the components or parts under the provision that the system is used as intended In an emergency or if there is a fault or other irregularities switch the equipm...

Страница 7: ...P 2015 Catalog item number Test date CE mark Grounding Series perm temperature time in smoke extraction perm temperature in continuous operation DVN D F4 400 C 120 min 20 C bis 200 C DVNI D F4 400 C 1...

Страница 8: ...8 5 50 200 91 86 146916 163 0 DVNI 710 D6 F4 30 144626 400V 3 Y 50 2768 6 9 50 200 83 143654 144615 534 467 363 341 484 556 245 4x 9 213 6x M6x15 144616 534 467 363 341 484 556 245 4x 9 213 6x M6x15 1...

Страница 9: ...etermining the fan ener gy efficiency such as ducts that are not described in the measure ment category and not supplied with the fan Units Model ID number see nameplate ruck Ventilatoren GmbH Local D...

Страница 10: ...ion If moisture has penetrated into the original packaging remove it immediately Storage temperature between 5 C and 40 C Avoid severe temperature fluctuations If the product has been in storage for m...

Страница 11: ...e nozzle plate 4 with hexagonal screws and sealing washers 5 6 on roof socket DSF If required it is possible to install further accessories at this point see 11 3 Installation examples with accesso ri...

Страница 12: ...26383 DVNI D F4 EN Installation operating and maintenance instructions 11 3 Installation examples DSF DAS DAF Tube Roof fan DSF Tube DSF DAS DAF Tube Roof fan DVK DSF DVK DAS DAF Tube Roof fan DSF DVK...

Страница 13: ...g between the unit and the duct system Check all protective measures after the electrical connection work earthing resistance etc Motor current and motor power must not exceed the values stated on the...

Страница 14: ...e time For the delta circuit the shorting blades are connecting U1 with W2 V1 with U2 and W1 with V2 see Img Never connect both jumpers at the same time If in spite of the correct connection to the ma...

Страница 15: ...lectric motors heat up Under certain circumstances excessively high ambient or fluid temperatu res heavy contamination etc the motor temperature may exceed the safety limit of the electrically isolate...

Страница 16: ...6 months Check impeller rotation direction yearly Check flexible connections for leaks yearly Check impeller for imbalance yearly Check protective device for function yearly Motor Check externally for...

Страница 17: ...all the threaded studs 3 and screw them out completely Lubricate a threaded pin and screw it into the disassembly hole 4 2 Tighten the threaded pin until the clamping bush 1 is released from the hub...

Страница 18: ...given here depends strongly on the respective field of application as well as the environmental condi tions We recommend replacing these fans after reaching about 30 000 operating hours or 5 years Fa...

Страница 19: ...19 EN Notes www ruck eu...

Страница 20: ...nt 25 02 2019 mdnif_pb_05_en We reserve the right to make changes Language English ruck Ventilatoren GmbH Max Planck Str 5 D 97944 Boxberg Windischbuch Tel 49 0 7930 9211 300 Fax 49 0 7930 9211 166 in...