Real Time Automation, Inc.
32
1-800-249-1612
BACnet/IP Server Configuration: Manual Configure Mode
1)
To transition from Auto-Configure Mode to Manual Configure Mode, click the dropdown in the
middle of the BACnet/IP Server Configuration page and select Manual Configure.
a.
When prompted, click
OK
to confirm mode change or
Cancel
to remain in Auto-
Configure Mode.
b.
Once OK is clicked, there are two options for how to proceed.
i.
To keep the current data groups and object properties (includes any default object
names, units and COV) that are already configured, press
OK
.
-
You would want this option if you are adding additional data groups or you
want to modify the data group(s) that already exist.
ii.
To delete the current data groups and object properties (includes any default object
names, units and COV) that are already there and start over, press
Cancel
.
2)
For each object type in the read and write data groups sections, select the number of objects
that the server will support.
3)
Each object has its starting object number sequentially identified at one. This field may be
modified.
4)
When done, click the
Save Parameters
button.
Содержание 460ESBS-N700
Страница 26: ...Real Time Automation Inc 26 1 800 249 1612...
Страница 30: ...Real Time Automation Inc 30 1 800 249 1612...