BACnet/IP Server Configuration-Data Groups
The bottom area of the BACnet/IP Server Configuration page lets you configure multiple objects for read
and write groups.
There are two ways to configure this protocol:
1)
Auto-Configure Group by Data Type (Default)
2)
Manual Configure Mode
NOTE
: You may go back and forth between modes, but when reverting from Manual Configure Mode to
Auto-Configure Mode, all changes made in Manual Mode will be discarded.
The setup in the example above will give you the following results:
•
1 AI is created with the address of AI1
•
8 BIs are created with the addresses BI1 through BI8
•
500 AOs are created with the addresses AO1 through AO500
•
1 CSV is created with the address of CSV51