5.4 Single or Dual Fire Alarm Dip-switch
Position up:
In single mode the extinguisher(s) will be released when one of the zones will have
a fire alarm condition.
Position down:
In dual mode the extinguisher(s) will be released after both zones will have a fire
alarm condition.
More information about this setting see paragraph 2.6.
5.5 Single or Dual VFC Dip-switch
Position up:
In the single mode the Voltage Free Contact (VFC) will be activated when one of the
zones will have a fire alarm condition.
Position down:
In the dual mode the Voltage Free Contact (VFC) will be activated after both zones
will have a fire alarm condition.
5.6 Timer Dip-switches
For the timer settings we have 3 dip-switches, which can be set between 0 and 30 seconds, with steps
of 5 seconds.
The table below shows the dip-switch settings for each step of 5 seconds is.
Dip-switch
Time
2
3
4
On
On
On
Immediate Release
On
On
Off
5 sec.
On
Off
On
10 sec.
On
Off
Off
15 sec.
Off
On
On
20 sec_
Off
On
Off
25 sec.
Off
Off
On
30 sec_
Off
Off
Off
No auto-release
More information about this setting see paragraph 2.7.