40
FA ROTEX RoCon mb • 09/2017
6
x
Parameter settings
6
Parameter settings
6.1
Explanation of the parameter tables
The parameter tables listed in Chaps. 6.2 to 6.11 include
compact information on all parameters, which is available in the
respective rotary switch setting on the control unit (1st menu
level, 2nd menu level).
In addition to the parameter designations, the tables contain de-
tails of the setting ranges, factory settings, setting options or
setting step distances and brief function explanations.
In addition, they provide explanation of the access rights for op-
eration of the control unit. The following abbreviations are used
for corresponding labelling:
Status:
6.2
Rotary switch setting: Configuration
6.2.1 "Setup" level
BE
Access right for the operator
HF
Access authorisation with technician code
In the event of different information in the BE and HF
columns, login as a heating technician must be carried
out prior to selecting the parameter level in order to
obtain the status entered in the HF column (see
chap. 3.6.1).
N
Not visible
E
Visible and configurable
S
Visible
Sub
-
lev
e
l
Parameters
Description
Access
Setting range
Min / Max
Factory
setting
Incre-
ment
BE
HF
LCD Brightness
Brightness of the display
E
E
0 - 100 %
50 %
10 %
LCD Illum Time
Lighting duration of the display
E
E
5 - 120 s
30 s
1 s
Language
National language of the display texts on the control unit
E
E
German
English
French
Dutch
Italian
Spanish
Portuguese
German
-
Date
Current date in day/month/year format. The current day of the week is calculated auto-
matically from the date.
E
E
Time
Time in hours/minutes format.
E
E
Keylock Function
Release of the key lock function:
Off: Key lock cannot be activated.
On: Key lock can be activated with the rotary button (see chap. 3.3).
E
E
Off
On
Off
-
Access Rights
Access code entry. Setting digit-by-digit like a combination lock (see chap. 3.6.1).
E
E
0 - 9
0000
1
RoCon U1 assign
Display only on connected
room station:
Function of the RoCon U1 room station in the CAN data bus system:
Living Room: Control unit for the heating circuit allocated in the [HC Assignment] param-
eter.
Mixing Valve: Mixer circuit operating unit (as mixer circuit extension or as a free-standing
mixer circuit control unit)
In addition to the above functions, the room station can basically be used as a remote
control unit for the ROTEX HPSU monobloc compact and the entire RoCon system (with
activated terminal function) (see chapters 4.1 and 4.4.2).
N
E
Living Room,
Mixing Valve
Living Room
-
Master-RoCon
Display only on connected
room station:
Setting of the master RoCon function
Off: Deactivated
On: Function active
For every RoCon U1 room station whose heating circuit ID is set on a direct heating cir-
cuit, the master RoCon function can be activated (see chap. 4.4.4). Several room sta-
tions with active master RoCon function in the system are possible, but only one room
station which is assigned to the same heat generator.
All settings on the RoCon U1 room station work for activated master RoCon function as
settings on the RoCon B1 control unit of the assigned heat generator. As a result, the
functions for hot water generation can also be remotely operated from the room station.
N
E
Off
On
Off
-
Outdoor type
Heat pump outdoor unit type
0: no selection
1: 5 kW
2: 7 kW
N
E
0 - 6
0
1
INDOOR UNIT
Heat pump interior unit type
Adaptation of the set value important, as the device types have different defrosting log-
ics.
0: no commissioning carried out so far.
1: 300
2: 500
N
E
0 - 4
0
1