FA ROTEX RoCon mb • 09/2017
6
x
Parameter settings
Max T-Out Cooling
Only applicable if the assigned heat generator has a cooling function
.
Only if [HC Function] parameter = 0:
Setting of the outside temperature at which the lowest target cooling feed temperature [T-Flow
Cooling max] is specified (setting condition: "Cooling" operating mode).
E
E
20 - 45 °C
35 °C
1 °C
T-Flow Cooling start Only applicable if the assigned heat generator has a cooling function
.
Only if [HC Function] parameter = 0:
Setting of the target cooling feed temperature at the start of cooling mode (outside temperature
= parameter [Start T-Out Cooling])
E
E
5 - 25 °C
18 °C
1 °C
T-Flow Cooling max Only applicable if the assigned heat generator has a cooling function
.
Only if [HC Function] parameter = 0:
Setting of the minimum target cooling feed temperature. This is held constant as of the outside
temperature ([Max T-Out Cooling] parameter).
E
E
5 - 25 °C
18 °C
1 °C
Min T-Flow Cooling
Only applicable if the assigned heat generator has a cooling function
.
Only if [HC Function] parameter = 0:
Setting of the absolute lower limit of the target cooling feed temperature. Limitation acts if a
lower target cooling feed temperature is determined from other parameter settings.
N
E
5 - 25 °C
18 °C
1 °C
T-Flow Cooling
Only applicable if the assigned heat generator has a cooling function
.
Only if [HC Function] parameter = 1:
Setting of the target cooling feed temperature (fixed value) for active cooling mode.
E
E
8 - 30 °C
18 °C
1 °C
Cooling Setpoint adj Only applicable if the assigned heat generator has a cooling function
.
Parallel shift of the cooling characteristic curve by the set value.
N
E
-5.0 to +5.0 kW
0.0 K
1 K
Relay Test
N
E
-
Screed
Function for screed drying
Off: Deactivated
On: the target feed temperature is regulated according to the set screed program. The day on
which the screed function is activated is not included in the running time of the screed program.
The first day starts when the day changes at 00:00 am. On the day of activation, heating is car-
ried out for the remaining time with the target feed temperature of the first day's program (see
chap. 3.6.13).
N
E
Off
On
Off
-
Screed Program
Setting of the sequence program of the screed heating. A separate target feed temperature can
be set for each day for a maximum duration of 28 days. The end of the screed program is de-
fined by the 1st day with the target value setting "- - - -" (see chap. 3.6.13).
N
E
10 - 70 °C per
heating day
See
1 °C
Tab. 6-16
Parameters in the "Configuration" rotary switch setting, "Mixer Config" level
Parameters
Description
Access
Setting range
Min / Max
Factory
setting
Incre-
ment
BE
HF