 Parameter settings

6.2.2 "System Configuration" level

Parameters

Description

Access

Setting range

Min / Max

Factory 

setting

Incre-

ment

BE

HF

Power DHW

Heat output of the electric heater booster for hot water preparation

N

E

1000 - 

40,000 W

3000 W

1000 W

BUH s1 power

Heat output of the electric heater booster for heating support stage 1
See operating instructions for heating element BUxx.

N

E

-

-

-

BUH s2 power

Heat output of the electric heater booster for heating support stage 2
See operating instructions for heating element BUxx.

N

E

-

-

-

Power BIV

Setting limits the heating support output.

N

E

3000 - 

40000 W

15000 W

1000 W

TDiff-DHW CH Sup-
port

Only if parameter [HZU] = On.
Heating support is activated if
Tdhw > T

HZUmin 

+ 4 K 

and

 Tdhw > [T-HS Setpoint] + 1 K.

Heating support is deactivated if 
Tdhw < T

HZUmin 

or

 Tdhw < [T-HS Setpoint].

T

HZUmin

 = currently active target hot water temperature [T-DHW Setpoint] + set parameter val-

ue [TDiff-DHW CH Support].
Tdhw = current hot water storage tank temperature
[T-HS Setpoint] = currently active target feed temperature (see tab. 6-12 and chap. 3.6.4)

N

E

2 - 15

5

1

T vbh1 max

Setting limits the target feed temperature (measured against t

V, BH

) when the heating support 

function is active.

N

E

5 - 85 °C

60 °C

1 °C

Equilibrium Temp

Setting influences the effect of the potential-free AUX switching contact (toggle switch output 
A) defined in the parameter [AUX Fct].

Only if parameter [Equilibrium Func.] = On:
Outside temperature as of which the optional heater booster is activated to support room heat-
ing. The bi-valence temperature is relevant to operation of the optional heater booster due to 
a backup requirement (room heating mode). The temperature of the temperature sensor (info 
value TA) integrated in the heat pump outdoor unit is used for this.

E

E

-15 to +35 °C

0 °C

1 °C

Function BSC

Selection of the functionality of switching contact EXT (J8):
0: evaluation of the resistance valves (see chap. 3.4.2)
1: evaluation as a burner blocking contact. If the switching contact is closed, the external heat 
generator has priority.

S

E

0 - 1

0

-

Quite Mode

Mode for low-noise operation at reduced output (see chap. 3.4.11).
0: deactivated
1: activated
2: only operated in whisper mode at night from 22:00 to 06:00 hours.

E

E

0 - 2

0

-

Quiet level

On selection of low-noise operation, three noise levels can be set.
0: less quiet. The output can decline in colder ambient conditions.
1: medium quiet. Reduced output is possible under all conditions.
2: quietest. The output is reduced under all conditions.

S

E

0 - 2

0

-

AUX Fct

Setting assigns the switching conditions for the potential-free AUX switching contact (toggle 
switch output A, see chap. 3.6.9).
0: function deactivated
AUX switching contact switches;
1: if storage tank temperature (Tdhw) 

 value of parameter [T-DHW 1 min].

2: if a cooling request or heating request is present.
3: if a hot water request to the backup heater (BUxx) is present or the configured backup heater 
is requested for heating support.
4: if an error is pending.
5: if the sensor value (TVBH) is > 60 °C.
6: if the outside temperature is < parameter value [Equilibrium Temp].

Heat pump continues to operate = parallel bi-valence mode.

7: if the outside temperature is < parameter value [Equilibrium Temp] + a heating request or a 
hot water request is present.

Heat pump does not continue to operate = alternative bi-valence mode.

8: if a hot water request is present.

9: if the outside temperature is < parameter value [Equilibrium Temp] + heat request "room 
heating" (not for hot water request). Heat pump no longer operates in room heating mode be-
low the value set in the parameter [Equilibrium Temp] - only in hot water mode.
Application: alternative room heating bi-valence mode if the boiler is hydraulically integrated so 
that it directly heats the unpressurised storage tank water of the ROTEX HPSU monobloc com-
pact (connection via solar connections).

10: "multi-oil" - if the outside temperature is < parameter value [Equilibrium Temp] + heat re-
quest "room heating" (not for hot water request). Heat pump no longer operates in room heat-
ing mode below the value set in the parameter [Equilibrium Temp] - only in hot water mode.
Application: alternative room heating bi-valence mode if the boiler is hydraulically integrated in 
the heat pump feed. For this application type, the frost protection function must be deactivated 
on the ROTEX HPSU monobloc compact (parameter [T-Frost Protect] = Off).

11: if the heat pump is in "Cooling" operating mode.

N

E

0 - 9

0

1

AUX time

AUX switching contact (A) only switches after a delay if the switching condition (see parameter 
[AUX Fct]) is present for longer than the set time.

N

E

0 - 600 s

120 s

5 s

T-DHW 1 min

Storage tank temperature (Tdhw) switching threshold for AUX switching contact (see parame-
ter [AUX Fct]).

N

E

20 - 85 °C

50 °C

1 °C

Delta-T CH

Target spread for room heating. The heating circulation pump of the ROTEX HPSU monobloc 
compact regulates the flow rate to achieve the target spread stored in the parameter between 
the target feed temperature and return temperature (t

V, BH

 - t

R1

).

N

E

2 - 20 K

7 K

1 K

Содержание RoCon M1

Страница 1: ...mpanies ROTEX Control unit RoCon mb RoCon U1 RoCon M1 Operating instructions Electronic controller for heat pumps For ROTEX HPSU monobloc compact types RKHWMX300C RKHWMX500C RKHWMXB300C RKHWMXB500C GB...

Страница 2: ...RoCon U1 room station 34 4 4 3 Allocating the RoCon M1 mixing module to a heat generator 35 4 4 4 Master RoCon function 35 4 4 5 Caretaker function 35 5 Parameter overview 36 5 1 For first commission...

Страница 3: ...tion 56 7 3 EHS emergency operation 56 7 4 Malfunctions and fault codes 56 8 Glossary 57 9 Notes 58 9 1 User specific settings 58 9 1 1 Switching time program 58 9 1 2 Parameters 59 9 1 3 IDs in the R...

Страница 4: ...ive installation and operating instruc tions On connection of a ROTEX HP convector the respective installation and operating instruc tions For connecting to another ROTEX heat gen erator or optional a...

Страница 5: ...gulations as well as the recognised safety related and occupational health rules 1 4 Use as intended The RoCon mb controller must only be used in ROTEX HPSU monobloc compact heat pumps that are approv...

Страница 6: ...at is installed on the north side of the building weather dependent T HS control can be further optimised If the optional RoCon G1 gateway 15 70 56 is installed and connected to the Internet the ROTEX...

Страница 7: ...t feed temperatures over 50 C the effi ciency COP of the ROTEX HPSU monobloc compact can de teriorate depending on the outside temperature 1 Clear text display 2 Setting Configuration 3 Setting Remote...

Страница 8: ...temperature tV BH is dis played beneath this 5 Mixer circuit The current T HS of the assigned heating circuit is displayed underneath 5 Room temperature sensor The current room temperature is display...

Страница 9: ...guage with the rotary button Confirm the selection with a brief push of the rotary button If the system is switched on the defaults set in the RoCon mb control unit fully automatically control the ope...

Страница 10: ...n the rotary button can be used to query all system temperatures the ROTEX HPSU monobloc compact type various software information and the operating states of all system components in succession The n...

Страница 11: ...r Interlink fct On priority Frost protection only IL1 Normal target feed temperature IL2 In heating mode increased target feed temperature In cooling mode reduced target feed tem perature Pump Current...

Страница 12: ...ition An overview is displayed Use the rotary button to select the required operating mode Confirm the selection with a brief push of the rotary button ROTEX HPSU monobloc compact operates according t...

Страница 13: ...e carried out with priority after activation only with technician code Tab 3 7 Overview of temporary time programs Fig 3 8 Standard display in the Standby operating mode above the frost limit temperat...

Страница 14: ...et tem perature set as default in the parameter T DHW Setpoint 1 The heating up is carried out with priority and independent of other heating programs Set the rotary switch to the DHW Install position...

Страница 15: ...Saturday to Sunday and Monday to Sunday Program Time period Switching cycle HC Program 1 Individual weekday Monday Tuesday 1 2 3 06 00 22 00 Working week Monday to Friday 1 2 3 06 00 22 00 Weekend Sat...

Страница 16: ...ay One time calendar controlled presence Control is carried out only according to the settings for Sunday in the HC Program 1 The hot water generation is only controlled according to the settings for...

Страница 17: ...tion see also chap 4 3 The local control unit functions as a remote control for the ex ternal device In this case all the control functions are performed and saved 1 1 as on the external device The di...

Страница 18: ...inte nance instructions If glycol has been added to the system the RoCon controller setting must be adapted accordingly Set the rotary switch to the Configuration position An overview is displayed Use...

Страница 19: ...h of the rotary button The setting of the parameter is displayed Set the parameter Parameter Emergency BUH 0 no automatic emer gency operation Parameter Emergency BUH 1 automatic emergency operation C...

Страница 20: ...push of the rotary button Manual Operation is active Use the rotary button to set the target feed temperature During active manual mode the storage tank temperature is permanently regulated to the fir...

Страница 21: ...factory in such a way that the heat slope does not independently adjust itself during operation Automatic heat slope adaptation can be activated parameter HC Adaption if the room station RoCon U1 15...

Страница 22: ...hem in small increments Deactivate the external heat sources e g stoves direct sunlight open windows Fully open any radiator thermostat valves or actuators Activate Heating operating mode Approximate...

Страница 23: ...loc compact is transmitted to the mixer module via the CAN bus or as a b Mixer add on with zone control A separate outside temperature sensor must be connected RKRSCA1 14 10 39 to the mixer module The...

Страница 24: ...iled explanations and possible setting values of this function can be found in chap 6 2 1 3 6 7 Additional alternative heat generator The heat supplied by an alternative WEZ must be fed to the un pres...

Страница 25: ...p does not continue to operate alternative bi valence mode 8 if a hot water request is present 9 if the outside temperature is parameter value Equilibrium Temp heat request room heating not for hot wa...

Страница 26: ...3 Execute the program by briefly pressing on the rotary button The respective values are reset to the factory setting 4 Use the rotary button to select Return 5 Confirm the selection with a brief pus...

Страница 27: ...tarted screed program can be deactivated at any time After ending the screed program the parameter is automat ically set to Off and the heating circuit continues to operate ac cording to the currently...

Страница 28: ...displayed Use the rotary button to select the HC Configuration level An overview is displayed Use the rotary button to select the Screed Program parameter Check the settings for the screed program an...

Страница 29: ...ing time program Here the circulation pump is controlled in parallel to the operating times of a hot water switching time program Independent of the set switching time program the energy con sumption...

Страница 30: ...Remote control via Internet An optional gateway RoCon G1 15 70 56 can be used to connect the RoCon mb controller to the Internet This enables remote control of the ROTEX HPSU monobloc compact by mobil...

Страница 31: ...ted in this chapter the specific commissioning instructions listed in the respective installation instructions for the ROTEX HPSU monobloc compact must be observed ID Function System components Parame...

Страница 32: ...tab 6 14 In the case of the RoCon U1 room station after setting the user language the Setup Wizard installation menu appears The items for defining the function the authorisation and the IDs of the r...

Страница 33: ...e heat generator or a RoCon U1 room station 15 70 34 After selection and confirming an external device the terminal function for this device is activated and the associated standard display for this d...

Страница 34: ...rameter is displayed Use the rotary button to set the Terminaladress parameter Confirm the selection with a brief push of the rotary button The standard display is shown see fig 4 4 The settings on th...

Страница 35: ...ed Use the rotary button to set the parameter for the function to On and confirm by pressing the rotary button briefly All settings on the RoCon U1 room station act in the same way as settings on the...

Страница 36: ...irst time or has been com pletely reset During initial commissioning After resetting to factory settings Rotary switch setting Info Resetting to factory settings see chap 3 6 12 Option 3 Rotary switch...

Страница 37: ...ressure Mode SG Max Pressure HT NT Function Set Point Pressure HT NT Contact Max Pressuredrop Room thermostat Relay Test Interlink fct MF 1 Config Air Purge PWM Config Emitter type Pump dT heating Pum...

Страница 38: ...5 2 6 Rotary switch setting DHW Set Temp T DHW Setpoint 1 T DHW Setpoint 2 T DHW Setpoint 3 5 2 7 Rotary switch setting Time Program Party Away HC Program 2 Vacation DHW Program 1 Holiday DHW Program...

Страница 39: ...oCon U1 assign Master RoCon PWM Config Min Perform Pump Max Perform Pump Sensor Config Tamb Config Outside Temp Adap Terminaladress Boiler Assignment HC Assignment Mixer Config HC Function Pump Mode T...

Страница 40: ...e key lock function Off Key lock cannot be activated On Key lock can be activated with the rotary button see chap 3 3 E E Off On Off Access Rights Access code entry Setting digit by digit like a combi...

Страница 41: ...mp is shut off no frost protection func tion see chap 3 6 5 or operated at higher temperatures N E 0 1 0 Mode SG Only if SMART GRID parameter 1 Used for a possible increase in the target temperature i...

Страница 42: ...nt is pending for the direct heating circuit of the heat generator N E 0 3 2 1 Air Purge Activation of automatic ventilation of the ROTEX HPSU monobloc compact and the con nected heating circuit see c...

Страница 43: ...basic configuration appropriate to the installed heat generator is automatically activated Confirmation of this parameter with the rotary button when Inactive or Delete is set leads to re initialisat...

Страница 44: ...Reduced output is possible under all conditions 2 quietest The output is reduced under all conditions S E 0 2 0 AUX Fct Setting assigns the switching conditions for the potential free AUX switching c...

Страница 45: ...circulation pump output pump Relay 2 output J14 circulation pump mix valve open Relay 3 Contact A on output J2 3UVB1 switching valve mix valve Closed Relay 4 Contact B on output J2 3UVB1 switching val...

Страница 46: ...Flow Day Only if HC Function parameter 1 Setting of the target feed temperature for the heating circuit during the heating time in operating mode Automatic 1 Automatic 2 Heating E E 20 90 C 40 C 1 C...

Страница 47: ...controlled according to the Circulation Time switching time program On Optional circulation pump is synchronously controlled to the active switching time program for hot water generation E E Off On Of...

Страница 48: ...respective target room temperature Hot water generation is carried out according to DHW Program 1 E E Automatic 2 The internal heating circuits regulate according to the set time program HC Program 2...

Страница 49: ...ay to Sunday can be parametrised E E See chap 3 4 7 See tab 3 9 15 min DHW Program 2 In this menu the 2nd time program for hot water generation can be parametrised 3 switching cycles with a resolution...

Страница 50: ...Wh S S kWh HS type The detected heat generator type ROTEX HPSU monobloc compact is displayed S S Sw Nr B1 U1 The software and the version of the RoCon B1 control panel the RoCon U1 room station are di...

Страница 51: ...r Function Setting of the system functionality of the device in the RoCon system do not change the factory setting The default value of this parameter is Single and thus applies to a ROTEX HPSU monobl...

Страница 52: ...for modulation of the pump power N E 0 100 50 1 Max Perform Pump Upper limit for modulation of the pump power N E 0 100 100 1 Sensor Config Tamb Config Configuration of the outside temperature sensor...

Страница 53: ...ed area of this room is determined the measured value can be cor rected by the set value E E 5 0 to 5 0 kW 0 0 K 1 K T Flow Day Only if HC Function parameter 1 Setting of the target feed temperature f...

Страница 54: ...N E 5 25 C 18 C 1 C T Flow Cooling Only applicable if the assigned heat generator has a cooling function Only if HC Function parameter 1 Setting of the target cooling feed temperature fixed value for...

Страница 55: ...ause of triggering the contactor and remedy fault Start the system again Once the cause has been remedied the system will resume operations as normal Contactor not triggered a No error codes are shown...

Страница 56: ...entitled Faults malfunctions mes sages To ensure that the error is not caused by incorrect set tings reset all parameters to the factory settings before any possible replacement of components see chap...

Страница 57: ...water from the radiators in the rooms back to the heat generator via the piping system Switching time program Setting of weekdays and times on the controller to define regular heating cooling economy...

Страница 58: ...d On Off On Off On Off HC Program 1 Monday Tuesday Wednesday Thursday Friday Saturday Sunday HC Program 2 Monday Tuesday Wednesday Thursday Friday Saturday Sunday Tab 9 1 Individual settings in the he...

Страница 59: ...9 5 IDs in the RoCon CAN bus system Switching cycle 1 Switching cycle 2 Switching cycle 3 Time period On Off On Off On Off Circulation Time Monday Tuesday Wednesday Thursday Friday Saturday Sunday Tab...

Страница 60: ...60 FA ROTEX RoCon mb 09 2017 9 x Notes 9 2 Other items...

Страница 61: ...9 x Notes FA ROTEX RoCon mb 09 2017 61...

Страница 62: ...62 FA ROTEX RoCon mb 09 2017 9 x Notes...

Страница 63: ...55 K Keylock 10 L Language setting 17 Low tariff mains connection 57 M Malfunctions 55 Manual operation 20 Master RoCon function 32 35 40 Mixer module 23 33 35 O Operating data overview 11 Operating...

Страница 64: ...ROTEX FA ROTEX RoCon mb Subject to change and correction 008 1442344_00 09 2017...

Отзывы: