ROTEX Heating Systems GmbH
8
The control system ensures the tap water temperature is correct. The water
temperature can be set between 40°C and 65°C (see par. 7.1). The set tap water
temperature is displayed on the operation panel. The standard setting is 60°C.
You can press the service button during tap water operation to read the actual tap water
temperature.
7
Heating up unit
In order to provide a fast supply of domestic hot water, a so-called tap comfort function
has been installed in the unit. This function keeps the heat exchanger at the right
temperature (this temperature can be set, see par. 7.2). The tap comfort function has
the following settings:
•
On: ( LED on) The tap comfort function of the unit is continuously switched on.
The unit always immediately provides warm water.
•
Eco: ( LED on) The tap comfort function of the unit is self-learning. The unit will
adjust to the usage pattern of the domestic hot water. This means the heat
exchanger will not be kept warm during the night or during longer absences.
•
Off: (Both LEDs off) The heat exchanger is not kept warm which means the supply of
domestic hot water takes a bit of time. If there is no need for fast delivery of domestic
hot water, the tap comfort function can be switched off.
In the settings “on” and “eco” , the unit meets the requirements of the Gaskeur
CW standards.
2.4
PC Interface
The boiler controller is provided with an interface for a PC. A PC can be connected by
means of a special dongle, and the associated software. This facility enables you to
follow the behavior of the boiler controller, the unit and the heat installation over a long
period.
2.5
Test programs
There is an option in the boiler controller, to bring the unit into a test status.
Activating a test program, will switch on the unit with a set fan rotations per minute,
without the control functions intervening.
The safety functions do remain active.
The test program is ended by pressing and simultaneously.
Test programs
Description of program
Button combination
Display reading
Burner on with minimum DHW
capacity (see parameter d par. 7.2)
and
“L”
Burner on with set maximum CH
power (see parameter 3 par. 7.2)
and (1x)
“h”
Burner on with maximum DHW power
(see parameter 3 par. 7.2)
and (2x)
“H”
Switching off test program
and
Current operation
situation
2.5.1
Frost protection
•
The unit is fitted with frost protection in order to prevent it from
freezing. If the temperature of the heat exchanger drops too low, the
pump will start running until the temperature of the heat exchanger
is sufficiently high. If the frost protection intervenes, code
7‘
will be
displayed (heating up exchanger).
•
If the installation (or a part thereof) can freeze, the coldest place
should be fitted with an (external) frost thermostat on the return pipe.
This must be connected in accordance with the electrical diagram
(see par. 10.1).
Note
When the unit is switched off (
-
on the service display) the unit frost protection will
remain active, however a heating request from an (external) frost thermostat will be
ignored.