4/9
Breadcrumb
Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
A.3.1.2.2.1
[9-05]
Temperature range
Minimum temp (heating)
R/W
15~37°C, step: 1°C
25°C
A.3.1.2.2.2
[9-06]
Temperature range
Maximum temp (heating)
R/W
37~depending on outdoor unit, step: 1°C
55°C
A.3.1.2.2.3
[9-07]
Temperature range
Minimum temp (cooling)
R/W
5~18°C, step: 1°C
5°C
A.3.1.2.2.4
[9-08]
Temperature range
Maximum temp (cooling)
R/W
18~22°C, step: 1°C
22°C
└──────────────────
Delta T source
A.3.1.3.1
[9-09]
R/W
3~10°C, step: 1°C
5°C
A.3.1.3.2
[9-0A]
R/W
3~10°C, step: 1°C
5°C
└─
Room thermostat
A.3.2.1.1
[3-07]
Room temp. range
Minimum temp (heating)
R/W
12~18°C, step: A.3.2.4
12°C
A.3.2.1.2
[3-06]
Room temp. range
Maximum temp (heating)
R/W
18~30°C, step: A.3.2.4
30°C
A.3.2.1.3
[3-09]
Room temp. range
Minimum temp (cooling)
R/W
15~25°C, step: A.3.2.4
15°C
A.3.2.1.4
[3-08]
Room temp. range
Maximum temp (cooling)
R/W
25~35°C, step: A.3.2.4
35°C
A.3.2.2
[2-0A]
R/W
-5~5°C, step: 0,5°C
0°C
A.3.2.3
[2-09]
R/W
-5~5°C, step: 0,5°C
0°C
A.3.2.4
R/W
0: 0,5 °C
1: 1 °C
└─
Operation range
14~35°C, step: 1°C
25°C (*5)
14~35°C, step: 1°C
35°C (*6)
A.3.3.2
[F-01]
R/W
10~35°C, step: 1°C
20°C
└─
Domestic hot water (DHW)
└─
Type
A.4.1
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
└─
Disinfection
A.4.4.1
[2-01]
R/W
0: No
1: Yes
A.4.4.2
[2-00]
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
A.4.4.3
[2-02]
R/W
0~23 hour, step: 1 hour
23
A.4.4.4
[2-03]
R/W
[E-07]
≠
1 :
55~80°C, step: 5°C
70°C
[E-07]=1 : 60°C
60°C
A.4.4.5
[2-04]
R/W
[E-07]
≠
1 : 5~60 min, step: 5 min
10 min
[E-07]=1 : 40~60 min, step: 5 min
4
0 min
└─
Maximum setpoint
A.4.5
[6-0E]
R/W
[E-07]
≠
1 : 40~80°C, step: 1°C
60°C
[E-07]=1 : 40~60°C, step: 1°C
60°C
└─
SP mode
A.4.6
R/W
0: Fixed
1: Weather dep.
└─
Weather dependent curve
A.4.7
[0-0B]
Weather-dependent curve
Leaving water value for high ambient temp. for
DHW WD curve.
R/W
35~[6-0E]°C, step: 1°C
55°C
A.4.7
[0-0C]
Weather-dependent curve
Leaving water value for low ambient temp. for
DHW WD curve.
R/W
45~[6-0E]°C, step: 1°C
60
°C
A.4.7
[0-0D]
Weather-dependent curve
High ambient temp. for DHW WD curve.
R/W
10~25°C, step: 1°C
15°C
A.4.7
[0-0E]
Weather-dependent curve
Low ambient temp. for DHW WD curve.
R/W
-40~5°C, step: 1°C
-10°C
└─
Heat sources
└─
Backup heater
A.5.1.1
[4-00]
R/W
0~2
0: Disabled
1: Enabled
A.5.1.3
[4-07]
R/W
0: No
1: Yes
A.5.1.4
[5-01]
R/W
-15~35°C, step: 1°C
0°C
└─
System operation
└─
Auto restart
A.6.1
[3-00]
R/W
0: No
1: Yes
└─
Preferential kWh rate
A.6.2.1
[D-00]
R/W
0: None
1: BSH only
2: BUH only
3: All heaters
A.6.2.2
[D-05]
R/W
0: Forced off
1: As normal
└─
Pwr consumpt. Control
A.6.3.1
[4-08]
R/W
0: No limitation
1: Continuous
2: Digital inputs
Allowed heaters
Forced pump OFF
Mode
Operation mode
Enable BUH step 2
Equilibrium temp.
Disinfection
Operation day
Start time
Temperature target
Duration
Room temp. step
A.3.3.1
[4-02]
Space heating OFF temp
R/W
Space cooling On temp
Heating
Cooling
Room temp. offset
Ext. room sensor offset
4P383508-1B - 2017.04
(*1) *HB*_(*2) *HV*_
(*3) *3V_(*4) *9W_
(*5) *04/08*_
(*6) *11/16*