11 Maintenance and service
Installer reference guide
77
RRLQ004~008CA + RHBH/X04+08CB
ROTEX HPSU low temperature Bi‑bloc
4P384979-1C – 2017.04
▪ Explain the user about energy saving tips as described in the
operation manual.
11
Maintenance and service
NOTICE
Maintenance must be done by an authorised installer or
service agent.
We recommend to do maintenance at least once a year.
However, applicable legislation might require shorter
maintenance intervals.
NOTICE
In Europe, the
greenhouse gas emissions
of the total
refrigerant charge in the system (expressed as tonnes
CO
2
-equivalent) is used to determine the maintenance
intervals. Follow the applicable legislation.
Formula to calculate the greenhouse gas emissions:
GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000
11.1
Overview: Maintenance and
service
This chapter contains information about:
▪ The yearly maintenance of the outdoor unit
▪ The yearly maintenance of the indoor unit
11.2
Maintenance safety precautions
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING
NOTICE: Risk of electrostatic discharge
Before performing any maintenance or service work, touch
a metal part of the unit in order to eliminate static electricity
and to protect the PCB.
11.2.1
Opening the indoor unit
See
"7.2.4 To open the switch box cover of the indoor unit" on
page 29
.
11.3
Checklist for yearly maintenance
of the outdoor unit
Check the following at least once a year:
▪ Outdoor unit heat exchanger.
The heat exchanger of the outdoor unit can get blocked up due to
dust, dirt, leaves, etc. It is recommended to clean the heat
exchanger yearly. A blocked heat exchanger can lead to too low
pressure or too high pressure leading to worse performance.
11.4
Checklist for yearly maintenance
of the indoor unit
Check the following at least once a year:
▪ Water pressure
▪ Water filter
▪ Water pressure relief valve
▪ Pressure relief valve of the domestic hot water tank
▪ Switch box
▪ Booster heater of the domestic hot water tank
Water pressure
Check whether the water pressure is above 1 bar. If it is lower, add
water.
Water filter
Clean the water filter.
NOTICE
Handle the water filter with care. Do NOT use excessive
force when you reinsert the water filter so as NOT to
damage the water filter mesh.
1
3
2
5
4
Water pressure relief valve
Open the valve and check if it operates correctly.
The water may be
very hot!
Checkpoints are:
▪ The water flow coming from the relief valve is high enough, no
blockage of the valve or in between piping is suspected.
▪ Dirty water coming out of the relief valve:
▪ open the valve until the discharged water does NOT contain dirt
anymore
▪ flush the system and install an additional water filter (a
magnetic cyclone filter is preferable).
To make sure this water originates from the tank, check after a tank
heat up cycle.
It is recommended to do this maintenance more frequently.
Relief valve of the domestic hot water tank (field supply)
Open the valve and check the correct operation.
Water may be very
hot!
Checkpoints are:
▪ The water flow coming from the relief valve is high enough, no
blockage of the valve or in between piping is suspected.
▪ Dirty water coming out of the relief valve:
▪ open the valve until the discharged water does not contain dirt
anymore
▪ flush and clean the complete tank, including the piping between
the relief valve and cold water inlet.
To make sure this water originates from the tank, check after a tank
heat up cycle.
It is recommended to do this maintenance more frequently.
Switch box
▪ Carry out a thorough visual inspection of the switch box and look
for obvious defects such as loose connections or defective wiring.