12 Troubleshooting
Installer reference guide
81
RRLQ004~008CA + RHBH/X04+08CB
ROTEX HPSU low temperature Bi‑bloc
4P384979-1C – 2017.04
Error code
Detailed error
code
Description
H6
00
OU: Malfunction of position
detection sensor.
Please contact your dealer.
H8
00
OU: Malfunction of compressor
input (CT) system.
Please contact your dealer.
H9
00
OU: Malfunction of outdoor
air thermistor.
Please contact your dealer.
F3
00
OU: Malfunction of discharge
pipe temperature.
Please contact your dealer.
F6
00
OU: Abnormal high pressure
in cooling.
Please contact your dealer.
FA
00
OU: Abnormal high pressure,
actuation of HPS.
Please contact your dealer.
JA
00
OU: Malfunction of high
pressure sensor.
Please contact your dealer.
J3
00
OU: Malfunction of discharge
pipe thermistor.
Please contact your dealer.
J6
00
OU: Malfunction of heat
exchanger thermistor.
Please contact your dealer.
L3
00
OU: Electrical box temperature
rise problem.
Please contact your dealer.
L4
00
OU: Malfunction of inverter
radiating fin temperature rise.
Please contact your dealer.
L5
00
OU: Inverter instantaneous
overcurrent (DC).
Please contact your dealer.
P4
00
OU: Malfunction of radiating
fin temperature sensor.
Please contact your dealer.
U0
00
OU: Shortage of refrigerant.
Please contact your dealer.
U2
00
OU: Defect of power supply
voltage.
Please contact your dealer.
U7
00
OU: Transmission malfunction
between main CPU- INV CPU.
Please contact your dealer.
Error code
Detailed error
code
Description
UA
00
OU: Indoor/outdoor combination
problem.
Power reset required.
Error codes of the indoor unit
Error code
Detailed error
code
Description
7H
01
Water flow problem.
7H
04
Water flow problem during
domestic hot water production.
Manual reset.
Check the domestic hot water
circuit.
7H
05
Water flow problem during
heating/sampling.
Manual reset.
Check the space heating/cooling
circuit.
7H
06
Water flow problem during
cooling/defrost.
Manual reset.
Check the plate heat exchanger.
80
00
Returning water temperature
sensor problem.
Please contact your dealer.
81
00
Leaving water temperature
sensor problem.
Please contact your dealer.
89
01
Heat exchanger frozen.
89
02
Heat exchanger frozen.
89
03
Heat exchanger frozen.
8F
00
Abnormal increase outlet
water temperature (DHW).
8H
00
Abnormal increase outlet
water temperature.
8H
03
Overheating water circuit
(thermostat).
A1
00
Zero cross detection problem.
Power reset required.
Please contact your dealer.