14 Technical data
Installer reference guide
88
RRLQ004~008CA + RHBH/X04+08CB
ROTEX HPSU low temperature Bi‑bloc
4P384979-1 – 2015.01
Removes dirt from the water to prevent damage to the pump
or blockage of the heat exchanger.
j
Pressure relief valve
Prevents excessive water pressure in the water circuit by
opening at 3 bar.
k
Refrigerant gas connection R410A
l
Refrigerant liquid connection R410A
m
Water inlet connection
n
Drain and fill valves
o
Shut-off valves (accessory)
Allows isolation of the indoor unit water circuit side from the
residential water circuit side.
p
Water outlet connection
q
Thermistors
Determines the water and refrigerant temperature at various
points in the circuit.
r
Backup heater thermal fuse
The fuse is blown when the temperature becomes higher
than the backup heater thermal protector temperature.
s
Backup heater thermal protector
The protector activates when the temperature of the backup
heater becomes too high.
t
Backup heater
Provides additional heating in case of cold outdoor
temperatures. Also serves as backup in case of
malfunctioning of the outdoor unit.
u
Air valve
14.4.4
Components: Switch box (indoor unit)
X4M
F1B F2B
TR1
X5M
X2M
X6Y
X6YA
X6YB
X1M
FU1
A1P
Q1L
K1M
K1M
X6M
X6M
X7M
X7M
K2M
K2M
K5M
K5M
K3M
K3M
d
d
a
b
c
c
d
e
p
g
h
i
k
j
q
f
s
r
o
n
m
l
a
Backup heater thermal protector Q1L
b
Transformer TR1
c
Terminals for backup heater X6M/X7M (*9W models only)
d
Backup heater contactors K1M, K2M and K5M
e
Booster heater contactor K3M (only for installations with a domestic
hot water tank)
f
Connectors X6YA/X6YB/X6Y
g
Backup heater circuit breaker F1B
h
Booster heater circuit breaker F2B.
i
Terminal block X2M (high voltage)
j
Terminal block X4M.
k
Terminal block X1M (to outdoor unit)
l
Cable tie mountings
m
Digital I/O PCB A4P (only for installations with digital I/O PCB kit)
n
Demand PCB for power limitation
o
Terminal block X5M (low voltage)
p
Socket X13A, receives the K3M connector.
q
Main PCB A1P
r
Socket X9A, receives the thermistor connector. (Only for installations
with domestic hot water tank)
s
PCB fuse FU1