The threshold 3 fault message is displayed when the limit threshold 3 is exceeded. The value
can be set from 0.1 to 20.0%.
End Set point Shift
Applicable for Posidapt
–
Super and Ultra
This parameter monitors whether the value of the upper end stop (open) has changed with
respect to its value at the time of calibration.
Ensure that the sub-
parameter "Open” in “Tight shut-off” parameter is set to “Custom”.
The current value is displayed in the "End set point shift" in Values and Counters under
Counter Thresholds and Trends. The device triggers a fault message if the current value
exceeds one of the three configurable limit thresholds.
Threshold Limit 1
Use this sub-parameter to set the factor for the formation of limit threshold 1.
•
Off - Factory default
This parameter value does not trigger any message or alarm.
•
Custom
The threshold 1 fault message is displayed when the limit threshold 1 is exceeded. The value
can be set from 0.1 to 20.0%.
Threshold Limit 2
Use this sub-parameter to set the factor for the formation of limit threshold 2.
Содержание Posidapt Expert
Страница 7: ...RTX IOM PRODUCT YY Page 7 of 131 www rotexautomation com 1 2 Posidapt Series...
Страница 17: ...RTX IOM PRODUCT YY Page 17 of 131 www rotexautomation com 4 Bock Diagram...
Страница 18: ...RTX IOM PRODUCT YY Page 18 of 131 www rotexautomation com 5 Dimensional Drawing...
Страница 30: ...RTX IOM PRODUCT YY Page 30 of 131 www rotexautomation com Figure 7 Attaching coupling and bracket to positioner...
Страница 44: ...RTX IOM PRODUCT YY Page 44 of 131 www rotexautomation com 7 Electrical Connection...
Страница 45: ...RTX IOM PRODUCT YY Page 45 of 131 www rotexautomation com 8 User Interface 8 1 Menu Structure Posidapt Expert...
Страница 46: ...RTX IOM PRODUCT YY Page 46 of 131 www rotexautomation com...
Страница 79: ...RTX IOM PRODUCT YY Page 79 of 131 www rotexautomation com...
Страница 122: ...RTX IOM PRODUCT YY Page 122 of 131 www rotexautomation com...