Valve Parameter
Tight shut-off Close
Applicable for Posidapt
–
Modern, Expert, Super, Ultra and IPST
This parameter is used to move the valve into its seat with the maximum force of the actuator.
•
Off
This parameter will deactivate the tight shut-off function at close position. This parameter
controls 0.0% (start position) of the device; the device is in controlled state.
•
Custom
– Factory Default
This parameter used for setting the tight shut-off value of start (close) position. The value can
be set from 0.0 to 20.0%.
Tight shut-off Open
Applicable for Posidapt
–
Modern, Expert, Super, Ultra and IPST
Содержание Posidapt Expert
Страница 7: ...RTX IOM PRODUCT YY Page 7 of 131 www rotexautomation com 1 2 Posidapt Series...
Страница 17: ...RTX IOM PRODUCT YY Page 17 of 131 www rotexautomation com 4 Bock Diagram...
Страница 18: ...RTX IOM PRODUCT YY Page 18 of 131 www rotexautomation com 5 Dimensional Drawing...
Страница 30: ...RTX IOM PRODUCT YY Page 30 of 131 www rotexautomation com Figure 7 Attaching coupling and bracket to positioner...
Страница 44: ...RTX IOM PRODUCT YY Page 44 of 131 www rotexautomation com 7 Electrical Connection...
Страница 45: ...RTX IOM PRODUCT YY Page 45 of 131 www rotexautomation com 8 User Interface 8 1 Menu Structure Posidapt Expert...
Страница 46: ...RTX IOM PRODUCT YY Page 46 of 131 www rotexautomation com...
Страница 79: ...RTX IOM PRODUCT YY Page 79 of 131 www rotexautomation com...
Страница 122: ...RTX IOM PRODUCT YY Page 122 of 131 www rotexautomation com...