Product Features
33
5.4 Using the wire controller to set
external static pressure
• You can use the unit’s automatic airflow adjustment
function to set external static pressure.
• Automatic airflow adjustment is the volume of blow-
off air that has been automatically adjusted to the
quantity rated.
1. Make sure the test run is done with a dry coil. If the coil
is not dry, run the unit for 2 hours in FAN ONLY mode to
dry the coil.
2. Check that both power supply wiring and duct
installation have been completed. Check that any closing
dampers are open. Check that the air filter is properly
attached to the air suction side passage of the unit.
3. If there is more than one air inlet and outlet, adjust
the dampers so that the airflow rate of each air inlet and
outlet conforms with the designed airflow rate. Make sure
the unit is in FAN ONLY mode. Press and set the airflow
adjustment button on the remote control to change the
airflow rate from H or L.
4. Set the parameters for automatic airflow adjustment.
When the air conditioning unit is off, perform the
following steps:
- When the unit is turned off, hold the MODE button and
FAN button down together for three seconds. (“AF”
indicator flashes for 3 times.)
- Press “
△
” or “
▽
” to select the AF.
- Press “MODE”. The air conditioning unit will then start
the fan for airflow automatic adjustment.
After 3 to 6 minutes, the air conditioning unit stops
operating once automatic airflow adjustment has finished.
Caution: DO NOT adjust the dampers when automatic
airflow adjustment is active.
Caution:
• If there is no change after airflow adjustment in the
ventilation paths, be sure to reset automatic airflow
adjustment.
• If there is no change to ventilation paths after airflow
adjustment,contact your dealer, especially if this occurs
after testing the outdoor unit or if the unit has been
moved to a different location.
• Do not use automatic airflow adjustment with remote
control,if you are using booster fans, outdoor air
processing unit, or a HRV via duct.
• If the ventilation paths have been changed, reset airflow
automatic adjustment as described from step 3 onwards.
5.5 Using the wire controller to set airflow
rate
When the air conditioning unit is off, perform the
following steps:
1. Press“MODE” and “FAN” for three seconds.
2. Press “
△
” or “
▽
” to select the SP.
3. Press “MODE” to set the airflow rate in the range of
0~4.
“0”: No airflow change
“1”~”4”:Airflow increase progressively
4. Press “ON/OFF” to finish the airflow setting.
Содержание ANERU Series
Страница 2: ......
Страница 5: ......
Страница 6: ...Contents 1 Precautions 2 2 Information servicing For flammable materials 3 Safety Precautions...
Страница 12: ...Contents 1 Model Reference 2 2 External Appearance 3 Model Reference...
Страница 15: ...Model Reference 4 2 2 Outdoor Unit Single Fan Outdoor Unit Double Fan Outdoor Unit...
Страница 18: ...IDU Console 3 2 Dimensional Drawings 16 Drain pipe Hanging arm 195 700 600 210...
Страница 21: ...IDU Console 6 6 Air Velocity and Temperature Distributions Discharge Angle 60...
Страница 36: ...IDU Compact Cassette 4 2 Dimensional Drawings...
Страница 38: ...IDU Compact Cassette 6 4 Service Place...
Страница 41: ...IDU Compact Cassette 9 Heating airflow velocity distributions Heating temperature distributions...
Страница 43: ...IDU Compact Cassette 11 Heating airflow velocity distributions Heating temperature distributions...
Страница 45: ...IDU Compact Cassette 13 Heating airflow velocity distributions Heating temperature distributions...
Страница 47: ...IDU Compact Cassette 15 Heating airflow velocity distributions Heating temperature distributions...
Страница 56: ......
Страница 115: ...IDU Super Slim Casstte 54 36k 42k 48k 55k...
Страница 118: ......
Страница 131: ...IDU Duct 7 6 Fan Performance 12K...
Страница 132: ...IDU Duct 8 18K...
Страница 133: ...IDU Duct 9 24K...
Страница 134: ...IDU Duct 10 30K 36K...
Страница 135: ...IDU Duct 11 42K 48K...
Страница 136: ...IDU Duct 12 55K...
Страница 165: ...IDU Duct 41 12k 18k 24k 30k...
Страница 166: ...IDU Duct 42 36k 42k 48k 55k...
Страница 178: ......
Страница 179: ...35mm 1 38in...
Страница 180: ......
Страница 256: ...IDU Floor Ceiling 82 36k 48k 55k...
Страница 259: ......
Страница 267: ...Outdoor Unit 3 Panel Plate B30...
Страница 268: ...Outdoor Unit 4 Panel Plate BA30...
Страница 269: ...Outdoor Unit 5 Panel Plate CA30...
Страница 270: ...Outdoor Unit 6 Panel Plate D30...
Страница 271: ...Outdoor Unit 7 Panel Plate X230...
Страница 272: ...Outdoor Unit 8 Panel Plate X330...
Страница 273: ...Outdoor Unit 9 Panel Plate X430...
Страница 274: ...Outdoor Unit 10 Panel Plate E30...
Страница 275: ...Outdoor Unit 11 Panel Plate 590...
Страница 276: ...Outdoor Unit 12 2 Service Place...
Страница 285: ...Outdoor Unit 21 UO70Xo UO90Xo UO100Xo UO100Xo3F...
Страница 286: ...Outdoor Unit 22 UO120Xo UO140Xo UO160Xo...
Страница 291: ......
Страница 292: ......
Страница 293: ......
Страница 294: ......
Страница 295: ...Outdoor unit printed circuit board diagram 17122000044714 17122000048121 17122000046453...
Страница 297: ...Outdoor unit printed circuit board diagram 17122000048064...
Страница 299: ...Outdoor unit printed circuit board diagram 17122000047742 1 3 4 6 8 9 5 7 10 12 11 2 13...
Страница 302: ...Outdoor unit printed circuit board diagram 17122000041841...
Страница 304: ...Outdoor unit DC motor driver board diagram 17122000021912 5 6 1 2 3 4...
Страница 320: ...3 IDU Installation Duct Connector Connector...
Страница 352: ...Product Features 13 Remote LCD Screen Indicators...
Страница 549: ......
Страница 550: ......
Страница 551: ......
Страница 552: ...email info rotenso com www rotenso com INSTALLER STAMP...