SuperGuard and Piguard Plus
|
1.09
46
9 CALIBRATION MENU
•
•
•
•
9.1 Temperature
This screen is used to calibrate temperature sensors.
TEMP. CALIB. #01
Temp-1(Factor)► 0.0
Temp-2(Factor) 0.0
Temp-3(Factor) 0.0
Temp-4(Factor) n/a
The temperature sensor is a very accurate sensor with a deviation of 0.1.
If required
, calibrate the
temperature sensor by using a very accurate reference instrument and enter the offset number for each
sensor in the Temp factor line. Use the up and down arrow keys to select sensors.
9.2 Humidity
This screen is used to calibrate humidity sensors.
HUM. CALIB. #01
Humid.(factor)► 0.0
If required
, calibrate the humidity sensor by using a very accurate reference instrument and enter the
offset number in the Humidity factor line.
9.3 Pressure
This screen is used to calibrate pressure sensors.
PRESS. CALIB. #01
Value A/D
Press ENTER to calib
9.4 Water & Feed
Water/feed #01
Water per pulse 0.1
Feed per pulse 1.0
The water and feed system operates on a pulse counting method. Enter the amount of feed/water per
pulse.