SuperGuard and Piguard Plus
|
1.09
34
•
From Level
: At what level the application starts
•
To Level
: At what level the application stops
If any of the definitions above is set on 0, the circulation fan operates at any time or level according to
the differential.
6.6 Cool Pad
The cooling table provides settings for the evaporative cool pad system. There are up to five fragments
allowing precise control over this system. Several fragments can be selected for the same day.
•
From
: (HH:MM) Start time.
•
To
: (HH:MM) End time.
•
Diff
: Differentiation from target temperature to activate cooling. When temperature raises diff
above target, cooling process will begin. When temperature reduces back to target, the
cooling process stops.
•
%RH
: As long as the hu Band are below this level the cooling operates. Cooling
stops only at humidity level + band. (See figure below)
•
On/Off
: (sec) On/Off cycle by seconds.
•
Band
: The cooling table has its own ‘happy zone’ for temperature and humidity that can be
set at the system parameters under cooling section. The cooling system turns on the amount
above specified in the column ‘Diff’ and turns off when the temperature drops the amount
specified in the band.
Cool Pad #01
#
From
To
Diff
%RH
On
Off
1
2
08:00
10:00
20:00
18:00
3.0
5.0
85
75
30
60
90
60
-
+
Band
Stop
Activate
RH%
-
+
Temp.
(Diff)
Activate
Stop
Temp
Band