Rotar Giga 75-100 - Cod.197AA3900 - Rev.03 - 05/2007

GB

9

9

9

9

9

CONTROLS AND SETTINGS

is from 0 to 150°C.

5) Minimum temperature (factory password): with this menu you can set the minimum temperature; the setting range is from

0 to -14°C.

6) Fan temperature (service password): with this menu you can adjust the temperature for activating the cooling fan; the

setting range is from 0 to 150°C.  At the preset temperature the fan starts; hysteresis is fixed at 10°C.

7) Duration of the idle running cycle (service password): with this menu you can change the duration of the machine idle

cycle; the setting range is from 60 to 900 seconds.

8) Stop Empty Cycle (assistance password): using this menu you can change the duration of the empty operating cycle

following the voluntary stopping of the compressor (OFF button), the range of regulation goes from 30 to 240 seconds.

9) Automatic start (service password): this parameter enables the automatic start; if it is activated, the compressor will restart

automatically following an interruption of the electrical power supply.

10) Internal phase sequence (service password): this parameter enables the internal phase sequence control, or disenables

the internal control by activating the input without phases on the terminal block.

11) Language (no password required): this parameter allows you to change the language in which messages are displayed.
12) RS485 enable (no password required): this parameter is used to enable data transmission via RS485 and automatically

disenable transmission on RS232.

13) Set time and date (no password required): used for setting the current time and date.
14) PSI/BAR (no password required): for selecting the unit of measurement used to display the pressure.
15) Idle/Operating pressure set point (no password required): this parameter is used to set the pressure at which the compressor

must shut down.

16) Load/Operating differential set point (no password required): indicates the pressure at which the control unit enables

compressor restart.

17) Maximum pressure (service password): this parameter sets the maximum pressure value that can be reached, i.e. the

maximum value set in point 14.

18) Maximum pressure alarm (factory password): this parameter sets the maximum pressure value at which the control unit

trips an alarm and blocks compressor operation.

19) Remote Pressure (assistance password): enabling this parameter, the visualisation of the pressure and respective

alarms is maintained, but the control of the start of the compressor takes place using an external pressure switch linked to a
dedicated digital entry. In this event, it is necessary to pay attention that the setting of the external pressure switch falls within
the values imposed in points 15 and 16. In case of an anomaly, an alarm message will appear.

20) Start programme (service password): this menu allows you to programme the starts and stops of the compressor. Use

  to select one of the five programmes available and press OK to enter the desired data (start time, stop time, and day of

the week).

To disactivate the programming, go to the menu and enter the same time of start and stop.
21) X1 progr. NC-NO  (service password): allows you to invert the logic of the inputs of terminal block X1.
22) X7 progr. NC-NO  (service password): allows you to invert the logic of the inputs of terminal block X7.
23) Motor therm. separate (service password): with the parameter ON, the thermal relays of the compressor and fan motors

are separated on two different inputs.

24) Temp. unit of measurement (no password required): for selecting the unit of measurement of the temperature (°C-°F).
25) Maximum starts per hour (service password): for selecting the maximum number of restarts per hour allowed. If this

value is exceeded, a signal is given.

The following menus are enabled only if an inverter is present:

26) Inverter
27) Minimum operation %
28) Load delay
29) Inverter integration
30) Inverter parameters

Parameter

min. max.

Def.

Parameter

min.

max.

Def.

0 ID

000

009

000 11 Language

ITA

1 General maintenance:

hours

0

50000 4000 12 RS485 enable 

YES

Air filter change:

hours

0

50000 2000 13 Time and date

Oil filter change:

hours

0

50000 4000 14 PSI/BAR

Bar

BAR

Oil change:

hours

0

50000 8000 15 Idle

Bar

0

P.Max.

10

Bearing lubrication:

hours

0

50000 4000 16 Load

Bar

0

2

0,5

Idle hours :

hours

0

50000

0

17 Maximum press ure 

Bar

0

P.all. - 0,5

11

Total working hours:

hours

0

50000

0

18 Maximum press ure alarm  Bar

0

16

14

3 Pre-alarm temperature

°C

0

20

5

19 Remote pres sure 

Bar

NO

4 Maximum temperature 

°C

0

110

110 20 Start programme 

OFF

5 Minimum temperature 

°C

-14

0

-7

21 X01 progr. NC-NO  

01 010110

6 Fan temperature 

°C

0

150

65

22 X07 progr. NC-NO  

111111

7 Idle running cycle 

sec.

60

900

180 23 Motor therm. separate 

NO

8 Stop Empty Cycle 

sec.

30

240

35

24 Temp. unit 

°C

9 Automatic start 

NO

25 Max. starts per hour 

1

200

12

10 Internal phase sequence 

NO

Содержание Giga 100

Страница 1: ...Rotar Giga 75 100 Cod 197AA3900 Rev 03 05 2007 GB use maintenance MANUAL Rotar Rotar Rotar Rotar Rotar Giga 75 100 Giga 75 100 Giga 75 100 Giga 75 100 Giga 75 100...

Страница 2: ......

Страница 3: ...1 oil drain tube no 1 door key no 1 user s guide CONDITION OF THE MACHINE WHEN SUPPLIED Every compressor is shop tested and delivered ready to be installed and to be set at work The oil used is RotEn...

Страница 4: ...ce and maintenance carried out so far SYMBOLS USED IN THE MANUAL Some symbols are used to highlight danger situations give recommendations or information These symbols are usually positioned next to t...

Страница 5: ...CE plate Always follow the maintenance schedule specified in the user s guide WHAT NOT TO DO Do not touch inner parts and pipes as they are very hot during compressor operation and stay hot for a cer...

Страница 6: ...tion of the machine Open the access doors and check all inner parts visual check Dispose of the packaging in compliance with the current waste disposal regulations PLACEMENT fig 2 The room chosen for...

Страница 7: ...the compressor heat energy as auxiliary heating unit These pipes should not be longer than 4 m Otherwise an auxiliary fan should be installed on the outlet side POWER CONNECTION Proceed to power conne...

Страница 8: ...takes you to the menu of operating parameters In certain cases a password is required in order to access the modifications Use the buttons to scroll the menu 0 Control unit ID service password selects...

Страница 9: ...ssure assistance password enabling this parameter the visualisation of the pressure and respective alarms is maintained but the control of the start of the compressor takes place using an external pre...

Страница 10: ...t verify the cause and then press the RESET button XX Emergency button Alarm tripped when the emergency button is pressed which blocks compressor operation To silence the alarm first reset the emergen...

Страница 11: ...filter replacement is required bearing lubric indicates the hours remaining until lubrication of the bearings is required oil filter h indicates the hours remaining until oil filter replacement is re...

Страница 12: ...il is returned to filter 11 through tube 10 From filter 11 oil reaches compressor 3 through tube 12 Oil is mixed with sucked air to form an air oil mixture that provides sealing and lubrication of com...

Страница 13: ...light for possible cuts replace element if any CHANGE THE AIR FILTER ELEMENT EVERY 3000 HOURS Undo retaining screws 3 from support panel 4 and remove prefilter Wash with water and soapy solution Fully...

Страница 14: ...ion fig 12 To perform this check you need a special measurement instrument that that provides a precise indication of the level of tension of the belt by means of a frequency measurement Proceed as fo...

Страница 15: ...STED OIL IS HIGHLY POLLUTANT Dispose of exhausted oil in compliance with current laws Used oil RotEnergy Plus Different compatible oil see table Service description Operating hours Operating hours Che...

Страница 16: ...emove and clean the intake regulator Oil mist separator filter clogged Replace the oil mist separator filter Line cock closed Open the cock Minimum pressure valve blocked Check and clean the valve if...

Страница 17: ...r no Ambient temperature C Noise level 1 m dB A Max compression temperature C Safety valve setting bar Separator pressure switch setting bar 8 9 10 9 8 9 10 9 Start up pressure switch setting bar Moto...

Страница 18: ...12 13 14 15 15 15 15 16 17 18 19 20 24 L22 L12 2 L31 L11 FU1 3 3 5 6 8 10 HL YV BULBO TERM THERM PROBE YV 5 25 AUTO DRAIN BULBO TERM THERM PROBE 3 3 PL1 PL2 10 8 6 5 12 13 22 021 ST2 BP V P V 021 22 2...

Страница 19: ...n pressure switch SA Radiator fan emergency control BP Line pressure transducer ST1 Screw delivery temperature probe ST2 Outlet air temperature probe D Electronic controller YV Solenoid valve M1 Upper...

Отзывы: