Programming
40
AC-F/G4x Series Installation and Programming Manual
5.8
Setting Fail Safe/Secure Operation
In this paragraph, the failsafe/fail secure operation of the door
lock and the Door Lock Strike Release time are set. Setting the
sounding period for the siren feature requires a BL-D40 external
sounder.
To set the Fail Safe/Secure Operation, Tamper Siren and Lock
Strike Release Time:
1.
Enter Programming mode.
2.
Press
6
to enter Menu 6.
The left LED flashes green.
3.
Construct a code using the following
instructions:
First digit
For Fail Secure Operation, the first digit should be
0
.
For Fail Safe Operation the first digit should be
1
.
Second digit
Siren Time in minutes (1–9, 0 – disabled)
Third and fourth digits
Enter the number of seconds (from 1 to 99) that you
want the Lock Strike to be released.
Green Green
Green