EC-Regler schaltet ab
¤)
Nicht vergessen den
Alarm mit Coil Stat Bit,
Adresse:1= ”1” rückzu-
stellen.
Reset (1 = Reset / pul-
se).
Der Alarm kann auch
durch ca. 60 Sek. Lan-
ges Abschalten des EC-
Reglers vom Netz rück-
gestellt werden.
Min. 2 Phasen an den
Motorklemmen sind kurz-
geschlossen
Kurzschluss an den Motorklemmen beheben ¤)
Defekter Motor
Motor austauschen ¤)
Überbelasteter Motor
Motor entlasten ¤)
Fault
Possible cause
Action
Motor inoperative
Lacking supply voltage
Check that the power supply is correctly con-
nected
to the EC Controller (terminals "L" and "N"
for 230 V models and terminals "L1", "L2" and
"L3" for 3 x 400 V and 3 x 230 V models).
Lacking operating signal
Coil Stat Bit, address = 0: Motor ON/OFF
(1=ON)
Poor electrical connec-
tions
Check pin connectors and all other electrical
connections.
Lacking speed setpoint
Holding Register, address=0; Setpoint / PrcSet ;
0-10000 ( 0-100%)
Internal motor protector
has cut out 5 times due
to overloading
Coil Stat Bit, address = 1: Reset (1 = Reset /
pulse) 0 – 1
The alarm can also be reset by disconnecting
the
power supply to the OJ Air2EC and reconnecting
it after approx. 60 seconds.
Defective EC Controller
Replace EC Controller
Defective motor
Replace motor
EC Controller makes
more noise than is ac-
ceptable
Switching frequency too
low
Raise switching frequency.
Holding Registers; address 10: SwitchMode; 0,
1, 2;
0 = Auto, 1 = 4 kHz, 2 = 8 kHz;
Raising the switching frequency increases ener-
gy
loss within the motor. The motor therefore be-
comes
less efficient and less economic to run.
EC Controller cuts out
¤)
Remember to reset the
alarm by setting
Coil Stat Bit, address:1=
At least 2 phases short-
circuited on motor termi-
nals
Remove short-circuit on motor terminals ¤)