Fan is not rotating or stops 
after a various time. 

No supply voltage present 
or missing of a single 
phase. 

Check the supply voltage 
directly on the fan.  

If not all phases are 

measureable check the-
fuses and the wiring of the 
service switch.

 

Fan turns but there is no 
or not enough airflow.

 

Rotation speed of the fan 
too low

 

Observe star / delta 
switching

 

Air flow interrupted

 

Check duct system  
(e.g. suction, filter, sealing 
caps).

 

Calculated pressure does 
not correspond to the real 
value.

 

Check fan selection.

 

Unfavorable installation 
conditions

 

Check the installation situ-
ation.

 

Vibrations / noises in fan.

 

Chafing of impeller

 

Chafing of impeller. Check 
impeller for dirt and clear-
ance. Check mounting of 
Impeller and inlet cone

 

Deformation

 

Stop fan immediately. 
Contact Rosenberg sup-
port

 

Dirty impeller

 

Clean impeller

 

Damaged ball bearings

 

an impeller. 
Damaged ball bearings. 
Stop fan immediately. 
Contact Rosenberg 
support 

RCD-Switch or fuse trips.

 

Ground fault or short 
circuit.

 

Check if the cables are 
damaged or 
moisture is present. 

Defect of the motor

 

Contact Rosenberg sup-
port

 

15 Notizen 

Notes 

 

Содержание DKN W E Series

Страница 1: ...sau Gaisbach Tel 49 0 7940 142 0 Fax 49 0 7940 142 125 Email info rosenberg gmbh com www rosenberg gmbh com Betriebsanleitung Operating instruction EHND Ex ERND Ex DKN_ W Ex DVWN Ex Explosionsgesch tz...

Страница 2: ...ess of producer 18 13 CE Kennzeichnung CE marking 19 13 1 Konformit tserkl rung Declaration of conformity 19 14 Fehlerfindung und Berichtigung Troubleshooting 24 15 Notizen Notes 25 2 Sicherheit Safet...

Страница 3: ...Radialventilator mit Normmotor und vorw rtsgekr mmten Laufrad ERND Ex Radialventilator mit Normmotor und r ckw rtsgekr mmten Laufrad EHND Ex Radialventilator mit freilaufendem Rad und Normmotor DKN_ W...

Страница 4: ...endungen bernimmt Rosenberg Ventilatoren GmbH keinerlei Haftung f r daraus resultierende Sch den In any case of divergence from the mentioned application or conditions of use Rosenberg Ventilatoren Gm...

Страница 5: ...ter 20 000 h or have to be regreased according to the manufacturer of the motor 3 The motor power for Ex fans type EHND ERND is limited on 11 kW 4 The fan is not gastight The place of installation mus...

Страница 6: ...vices Protection guards are available as accesso ries The requirements of DIN EN ISO 13857 and DIN EN ISO 12100 have to be met 5 1 Max Drehzahl Maximum speed Bei Standard Anwendung wird durch die Polp...

Страница 7: ...560 630 630 H 142 max Drehzah l seed 1 min 2 660 2 360 2 140 1 840 1 540 1 290 1 470 Laufradbreite reduziert auf 142 mm impeller breadth reduced to 142 mm Werden Frequenzumformer einge setzt sind druc...

Страница 8: ...tagehil fen wie z B vorschriftsm ige Ger ste Store the fan on a dry place and weather protected in its original pack ing Cover open palettes with a tarpaulin and protect the fans against influence of...

Страница 9: ...an geschlossen werden In hazardous areas connect components to a voltage equalizing system F r alle Radialventilatoren gilt Aufstellung im Au enbereich nur nach ausdr cklichem Vermerk und Best ti gung...

Страница 10: ...e fans at the angle frames or at the angle mounted feet Do not bend fans Bei Dachventilatoren ist zu beachten Bei dem Aufsetzen des Dach ventilators auf dem Dachsockel oder dem Sockelschalld mpfer ist...

Страница 11: ...e manufacturer Non horizontal shaft positions may reduce bearing lifetime At positions installed where small parts may fall into the cooling blade of the motor e g vertical motor shaft there must be a...

Страница 12: ...Zone vorhanden ist Insbesondere bei wasserstoffhaltiger Luft besteht er h hte Z ndgefahr durch statische Entladungen Ensure before any work that no Ex Zone is exists any more Particularly at presence...

Страница 13: ...greasing can be used These have to be regreased according to the re quirements of the manufacturer of the mo tor Change all non regreasable bearings after 20 000h Vor jeglichen Arbeiten am Ventilator...

Страница 14: ...der korrekte Einbau und die Funktion des Ventila tors zu berpr fen Den Hinweisen in Abschnitt 7 Montage ist unbedingt folge zu leisten After each repair and maintenance the correct mounting and operat...

Страница 15: ...bles 3 If necessary remove all liquids such as oil and remove this accord ing to the local requirements 4 Transport the machine to a suitable location for disassembly 10 2 Maschine zerlegen Dismantlin...

Страница 16: ...artonagen k nnen ohne weiteres der Werk stoffverwertung zugef hrt werden Verschmutzte Verpackungsmateria lien k nnen einer thermischen Ver wertung zugef hrt werden Cables and wires If applicable elect...

Страница 17: ...e g 16 of production 6 Kommentarfeld comments field 7 Kennzeichnungsfeld siehe unten identification field see below 8 Typenbezeichnung type designation 11 1 Kennzeichnungsfeld Marking field 10 9 11 12...

Страница 18: ...to special in this case restricted operating conditions See details in chapter 5 12 Kundendienst Herstelleradresse Service Address of producer Rosenberg Produkte unterliegen einer st ndigen Qualit ts...

Страница 19: ...ieht sich ausschlie lich auf gem der Be triebsanleitung angeschlossene und ei genst ndig betriebene Ventilatoren bei sinusf rmiger Stromversorgung Herewith we declare under our sole re sponsibility th...

Страница 20: ...20 BA019BB0618A25...

Страница 21: ...BA019BB0618A25 21...

Страница 22: ...sanleitung erw hnt wurden Rosenberg products are covered by the provisions of an incomplete machine Be cause of this the following declaration of incorporation has been created The decla ration of inc...

Страница 23: ...BA019BB0618A25 23...

Страница 24: ...rschlussklap pen Druckverlust entspricht nicht den berechneten Werten Auswahl Ventilator pr fen Ung nstige Einbauverh lt nisse Einbausituation ber pr fen Vibrationen Ger usche im Ventilator Laufrad st...

Страница 25: ...ressure does not correspond to the real value Check fan selection Unfavorable installation conditions Check the installation situ ation Vibrations noises in fan Chafing of impeller Chafing of impeller...

Отзывы: