Reference Manual
00809-0100-4727, Rev EA
October 2010
B-7
Rosemount 8700 Series
HAZARDOUS LOCATION
CERTIFICATIONS
Equivalent Hazardous Location Certifications for sensor and transmitter must match in
integrally-mounted magnetic flowmeter systems. Remote-mounted systems do not require
matched hazardous location certification option codes.
North American
Certifications
Factory Mutual (FM)
N0
Division 2 Approval for
Non-Flammable Fluids (All Sensors)
Class I, Division 2, Groups A, B, C, D
Temp Code – T5 (8705/8711 at 60 °C)
Temp Code – T3C (8707 at 60 °C)
Dust-Ignition proof Class II/III, Division 1, Groups E, F, G
Temp Code – T6 (8705/8711 at 60 °C)
Temp Code – T3C (8707 at 60 °C)
Enclosure Type 4X
N0 for 8721 Hygienic Sensor
Factory Mutual (FM) Ordinary Location;
CE Marking; 3-A Symbol Authorization #1222;
EHEDG Type EL
N5
Division 2 Approval for Flammable Fluids
(All Sensors)
Class I, Division 2, Groups A, B, C, D
Temp Code – T5 (8705/8711 at 60 °C)
Temp Code – T3C (8707 at 60 °C)
Dust-Ignition proof Class II/III, Division 1, Groups E, F, G
Temp Code – T6 (8705/8711 at 60 °C)
Temp Code – T3C (8707 at 60 °C)
Enclosure Type 4X
E5
Explosion-Proof (8705 and 8711 Only)
Explosion-Proof for Class I, Division 1, Groups C, D
Temp Code – T6 at 60 °C
Dust-Ignition proof Class II/III, Division 1, Groups E, F, G
Temp Code – T6 at 60 °C
Class I, Division 2, Groups A, B, C, D
Temp Code – T5 at 60 °C
Enclosure Type 4X
Canadian Standards
Association (CSA)
N0
Suitable for Class I, Division 2, Groups A, B, C, D
Temp Code – T5 (8705/8711 at 60 °C)
Temp Code – T3C (8707 at 60 °C)
Dust-Ignition proof Class II/III, Division 1, Groups E, F, G
Enclosure Type 4X
N0 for 8721 Hygienic Sensor
Canadian Standards Association (CSA) Ordinary Location;
CE Marking; 3-A Symbol Authorization #1222;
EHEDG Type EL
European Certifications
ND
ATEX Dust Certificate No.: KEMA 06ATEX0006
II 1D Ex tD A20 IP6x T105°C (-50
≤
T
amb
≤
65 °C)
0575
INSTALLATION INSTRUCTIONS
The cable and conduit entry devices and blanking elements shall be of a certified IP6x type,
suitable for the conditions of use and correctly installed. At maximum ambient temperatures or at
process temperatures above 60 °C heat resistant cables with a temperature rating of at least 90
°C shall be used.