Reference Manual
00809-0100-4727, Rev EA
October 2010
Rosemount 8700 Series
2-6
The electrodes in the Rosemount 8711 are properly oriented when the top of
the sensor is either vertical or horizontal, as shown in Figure 2-6. Avoid any
mounting orientation that positions the top of the sensor at 45 degrees from
the vertical or horizontal position.
Figure 2-6. Rosemount 8711
Mounting Position
Flow Direction
The sensor should be mounted so that the FORWARD end of the flow arrow,
shown on the sensor identification tag, points in the direction of flow through
the sensor (see Figure 2-7).
Figure 2-7. Flow Direction
45° Electrode Plane
45° Electrode Plane
FLOW