Reference Manual
00809-0100-4799, Rev BA
September 2002
A-3
Model 3244MV
Update Time
Approximately 0.5 seconds for a single sensor (1.0 second for two sensors).
Performance
The Model 3244MV with Profibus-PA maintains a specification conformance
of at least 3
.
Accuracy
Stability
±0.1% of reading or 0.1 °C, whichever is greater, for 24 months for RTDs.
±0.1% of reading or 0.1 °C, whichever is greater, for 12 months
for thermocouples.
Sensor Lead Wire Resistance Effect
RTD Input
When using a 4-wire RTD, the effect of lead resistance is eliminated and has
no impact on accuracy. However, a 3-wire sensor will not fully cancel lead
resistance error because it cannot compensate for imbalances in resistance
between the lead wires. A 2-wire sensor will produce the largest error
because it directly adds the lead wire resistance to the sensor resistance. For
2- and 3-wire RTDs, an additional lead wire resistance error is induced with
ambient temperature variations. Table A-2 and the examples shown below
help quantify these errors.
Sensor Options
Input Ranges
Accuracy
(1)
2-, 3-, 4-Wire RTDs
°C
°F
°C
°F
Pt 100 (
= 0.00385)
(2)
200 to 850
–328 to 1562
± 0.10
± 0.18
Pt 100 (
= 0.003916)
(3)
200 to 645
–328 to 1193
± 0.10
0.18±
Pt 200
200 to 850
–328 to 1562
± 0.22
± 0.40
Pt 500
200 to 850
–328 to 1562
0.14
± 0.25
Pt 1000
200 to 300
–328 to 572
± 0.08
± 0.14
Ni 120
(4)
200 to 300
–94 to 572
± 0.08
± 0.14
Cu 10
(5)
200 to 250
–58 to 482
± 1.00
± 1.80
Thermocouples
°C
°F
°C
°F
NIST Type B
(6)
(7)
(8)
212 to 3308
100 to 1820
± 0.75
± 1.35
NIST Type E
–58 to 1832
–50 to 1000
± 0.20
± 0.36
NIST Type J
–292 to 1400
–180 to 760
± 0.25
± 0.45
NIST Type K
–292 to 2502
–180 to 1372
± 0.50
± 0.90
NIST Type N
32 to 2372
0 to 1300
± 0.40
± 0.72
NIST Type R
32 to 3214
0 to 1768
± 0.60
± 1.08
NIST Type S
32 to 3214
0 to 1768
± 0.50
± 0.90
NIST Type T
–328 to 752
–200 to 400
± 0.25
± 0.45
Millivolt Input
(9)
–10 to 100 mV
± 0.015 mV
2-, 3-, 4-Wire Ohm Input
0 to 2000 ohms
±0.35 ohm
(1) The transmitter’s accuracy is valid for the entire input range of the sensor.
(2) IEC 751;
α
= 0.00385, 1995.
(3) JIS 1604, 1981.
(4) Edison Curve No. 7.
(5) Edison Copper Winding No. 15.
(6) NIST Monograph 175.
(7) Accuracy for NIST Type B T/C is ±3.0 °C (5.4 °F) from 100 to 300 °C (212 to 572°F).
(8) Total accuracy for thermocouple only: sum of ac0.25 °C (cold junction accuracy).
(9) Millivolt inputs are not approved for use with CSA option code I6.
Содержание 3244MV
Страница 2: ......
Страница 4: ......
Страница 46: ...Reference Manual 00809 0100 4799 Rev BA September 2002 Model 3244MV A 12 ...
Страница 58: ...Reference Manual 00809 0100 4799 Rev BA September 2002 Model 3244MV B 12 ...
Страница 60: ...Reference Manual 00809 0100 4799 Rev BA September 2002 Model 3244MV Index 2 ...
Страница 61: ......