Reference Manual
00809-0100-4799, Rev BA
September 2002
Model 3244MV
3-3
CONFIGURATION
Physical Block
1.
Place the physical block into “Out of Service (O/S)” mode.
2.
Select the “Display” mode, located under the “Device”
pull-down menu.
3.
Turn on the valves to be displayed. Set the desired decimal place.
4.
Download the device.
5.
Select the “Load into PG/PG” option (UPLOAD), located under the
“Device” pull-down menu.
6.
Place the Physical Block into Auto mode.
Transducer Block
1.
Select the “Master Reset” option, located under the “Device”
pull-down menu.
2.
Input the following as desired
•
1
to select restart with defaults
•
4
to restart processor
3.
Click “download” to download the device.
4.
Once the device has restarted, click close.
5.
Select “Change Sensor Type,” method located under the “Device”
pull-down menu. When this method begins, select the desired sensor
type and the connection.
6.
Perform step five for all sensors.
7.
Select the “Load into PG/PG” option (UPLOAD), located under the
“Device” pull-down menu.
8.
Place the transducer block into “Out of Service (O/S)” mode. Set the
filter time constant to the desired value (perform for all transducer
blocks).
9.
Select the “Load into PG/PG” option (UPLOAD), located under the
“Device” pull-down menu.
10. Place the Transducer block into Auto mode.
AI blocks
1.
Place the AI block into “Out of Service (O/S)” mode and
then UPLOAD.
2.
Configure the channel for each block by right-clicking on the
parameter for each block. Select “On-line Option” and then the
channel. Choose a option and UPLOAD.
3.
Right-click on the “Process Scale Variable” parameter. Indicate the
desired upper, lower and unit values. Download these parameters
onto the device (performed for each block). UPLOAD.
4.
Right-click on the “Output Signal” parameter. Indicate the desired
upper, lower and unit values. Download these parameters onto the
device (performed for each block).
5.
Select the “Load into PG/PG” option (UPLOAD), located under the
“Device” pull-down menu.
6.
To set User Warning and Alarm Limits, right-click on “Upper Limit
Alarm,” “Upper lImit Warning,” “Lower Limit Warning,” and “Lower
Limit Alarm.” Select values and UPLOAD.
7.
Place the AI block into Auto mode.
Содержание 3244MV
Страница 2: ......
Страница 4: ......
Страница 46: ...Reference Manual 00809 0100 4799 Rev BA September 2002 Model 3244MV A 12 ...
Страница 58: ...Reference Manual 00809 0100 4799 Rev BA September 2002 Model 3244MV B 12 ...
Страница 60: ...Reference Manual 00809 0100 4799 Rev BA September 2002 Model 3244MV Index 2 ...
Страница 61: ......