Reference Manual
00809-0100-4799, Rev BA
September 2002
Model 3244MV
3-8
5
TARGET_MODE
The TARGET_MODE parameter contains desired
mode normally set by a control application or an
operator.
R/W
Unsigned8
1
6.2
MODE_BLK.actual
These blocks contain the actual, permitted and
normal modes of the block
R
DS-37
3
6.3
MODE_BLK.permitted
6.4
MODE_BLK.normal
7
ALARM_SUM
This parameter contains the current states of the
block alarms
R
DS-42
8
8
MEAS_VALUE
Main measuring value, function of sensors/asic,
corrected by BIAS_
1
/
2
R
DS-33
5
11
SENSOR_MEAS_TYPE
Mathematical function: Normal, average,
differential form channel 1 and 2
R/W
Unsigned8
1
13
SENSOR_TYPE
Select the type of sensor (Code) for
Thermocouples, Rrd., Pyrometers or linear
R/W
Unsigned8
1
20
TEMPERATURE_UNIT
Select the unit of the temperature. (Example: °C,
°F, °K, %...), Coding according HCF
R
Unsigned16 2
21
UPPER_SENSOR_LIMIT
Maximum sensor temperature: Physical upper limit
function of sensor.
(Example: PT 100 = 850 °C)
R
Float
4
22
LOWER_SENSOR_LIMIT
Minimum sensor temperature: Physical lower limit
function of sensor.
(Example: PT 100 = –200 °C)
R
Float
4
23
MEASURE_FILTER
Measuring filter parameter to suppress noise in
process temperature.
R/W
Float
4
24
INPUT_FAULT
Used to indicate memory ASIC, communication, or
material failures.
R/W
Unsigned8
1
25
RJ_TEMP
Reference junction temperature
R
Float
4
26
RJ_TYPE
Select reference junction from internal to fixed
value
R/W
Unsigned8
1
27
RJ_VALUE
Fixed temperature value I, in degree, of reference
junction
R/W
Float
4
28
SENSOR_CONNECTION
The number of wires for the temperature probe.
Valid values are: 0 = 2 wire sensor, 1 = 3 wire
sensor, 2 = 4 wire sensor
R/W
Unsigned8
1
40
CAL_POINT_HI
The value of the Primary Value Measurement used
for the high calibration point.
R/W
Float
4
41
CAL_POINT_LO
The value of the Primary Value Measurement used
for the low calibration point.
R/W
Float
4
42
CAL_MIN_SPAN
The minimum span that must be used between the
calibration high and low points
R
Float
4
43
CAL_UNIT
The units used for the calibration inputs. Valid
calibration units are the following:
R/W
Unsigned16 2
35 = K
32 = °C
33 = °F
34 = °R
36 = mV
37 = Ohm
57 = Percent
250 = Not used
44
SENSOR_SN
Serial number of the sensor
R/W
Octet(32)
32
45
SENSOR_CAL_METHOD
The last method used to calibrate the device.
(Example: Factory calibration or user specified):
103 = Factory trip standard, 104 = User trim
standard
R/W
Unsigned8
1
46
SENSOR_CAL_LOC
The last location of the calibrated sensor
R/W
Octet(32)
32
PA Index
Number
Parameter
Description
Access
Data Type/
Structure
Size –
Bytes
Содержание 3244MV
Страница 2: ......
Страница 4: ......
Страница 46: ...Reference Manual 00809 0100 4799 Rev BA September 2002 Model 3244MV A 12 ...
Страница 58: ...Reference Manual 00809 0100 4799 Rev BA September 2002 Model 3244MV B 12 ...
Страница 60: ...Reference Manual 00809 0100 4799 Rev BA September 2002 Model 3244MV Index 2 ...
Страница 61: ......