25
INSTRUCTIONS FOR THE INSTALLER
21
Installation using flexible connection
As an option, the cooker may be installed with a
flexible connection hose, which complies with AS/
NZS 1869 (AGA Approved), 10 mm ID, class B or
D, Minimum 1000 mm - Maximum 1200 mm, as an
alternative connection.
• All cookers offer left or right hand connection. The
manifold has a flat flair over which is inserted a
screw nut male
½”
gas (fig 21A).
• An isolating tap and pressure regulator must be
fixed to the rear wall and the flexible pipe attached
by means of a union connector.
• The gas connection and isolating tap must be
accessible to a service person or inspector.
•
The hose assembly must be installed in accordance
with AS5601 for a high level connection. The hose
should not be subjected to abrasion, kinking or
permanent deformation and should be able to be
inspected along its entire length. Unions compatible
with the hose fittings must be used and connections
tested for gas leaks. The fixed consumer piping
outlet should be at approximately the same
height as the cooker connection point, pointing
downwards.
•
The hose should be clear of the floor when the
cooker is in the installed position. The hose restraint
chain supplied should be anchored to the lower
hook fixed to the wall so that the chain prevents
strain on the hose connections when the cooker is
pulled forward.
•
Before Leaving - Check all connections for gas leaks
with soap and water.
DO NOT
use a naked flame for
detecting leaks. Ignite all burners both individually
and concurrently to ensure correct operation of gas
valves, burners and ignition. Turn gas taps to low
flame position and observe stability of the flame for
each burner individually and concurrently. When
satisfied, please instruct the user on the correct
method of operation. In case the appliance fails to
operate correctly after all checks have been carried
out, refer to the authorised service provider in your
area.
GAS CONNECTION
This appliance shall be installed only by authorised
personnel and in accordance with the manufacturer’s
installation instructions, local gas fitting regulations,
municipal building codes, water supply regulations,
electrical wiring regulations, AS 5601 - Gas Installations
and any other statutory regulations.
The appliance is adjusted to work at gas indicated on the
label which is applied on the glass-window of the oven
door and on the cooker packing.
Installation for Natural gas
Connected regulator (B) to fitting (A) which is then fitted to
elbow (F). Ensure arrow on regulator point in the direction
shown. Fitting (D) to be supplied by installer (fig. 21).
Adjust regulator to give test-point pressure given on data
label
(see on
TECHNICAL FEATURES
paragraph)
,
with one large or one medium burner alight at maximum.
Position of Regulator (fig. 21)
The stove must be installed on legs, a gas pipe between
fitting (A) and (B) will allow location of the regulator (B)
underneath the stove for adjustment and maintenance
Installation for Propane Gas
Connect by using a copper pipe starting, from the threaded
fitting of elbow (F) .
Note: When the regulator is fitted at the rear of
the cooker at least 60 mm clearance is required.
21A
Содержание RR48DF-1-SS
Страница 1: ...Model RR48DF 1 SS Manual Use Care Installation ...
Страница 31: ...SPACE FOR DATA LABEL ...