The change of the reader to DISARMED state can be additionally indicated via the output line (to enable this, 
activate the Reader Disarmed Output option). Such configuration allows the output line to function as a driver 

to arm/disarm the connected alarm system or to operate (on/off) some other auxiliary system or device such 

as lights, heating hardware etc. In general, the reader’s ARMED/DISARMED states have no effect on unlocking 

the door, unless the 

Access Disabled When Reader Armed

 option has been enabled (see the C11 

configuration code programmed in Installer Programming Mode). With this option activated, access to the 

supervised room can be granted only if the reader is in disarmed state.  

Also, by activating this option TOGGLE Users obtain capability to enable/disable access to the supervised room, 

plus, it allows automatic locking upon a reader entering the ARMED state. 

Note: Upon powering on, the reader automatically returns to the ARMED/DISARMED state it was in before 

powered off. Also, the reader returns to its original ARMED/DISARMED state after exiting the programming 

mode. After Memory Reset the reader always enters ARMED mode. 

4.3

 

Arming and Disarming of the Reader (Reader Rearming) 

The action changing the reader’s state from ARMED to DISARMED and back is referred to hereinafter as 

REARMING. The term “arming” should be understood here as the action effecting a switch into the ARMED 

state, whereas the term “disarming” a switch into the DISARMED state. 

 

Reader rearming command can be issued by TOGGLE or TOGGLE LTD Users. To rearm the reader a TOGGLE 

user is required to read twice a TOGGLE card, whereas a  TOGGLE LTD user needs only one reading of his card 

at the reader.  

 

With an input line configured to be used as 

Ready Input

, the reader accepts arming user requests only if the 

input line receives an active signal. Consequently, when Ready Input is not triggered (passive state) the PRT6t2 

will reject any attempt to arm the reader. Typically the reader’s 

Ready Input

 line should be wired to the Alarm 

System Control Unit’s output designed to indicate that the Alarm System is ready for arming (“Ready Output” 

on an Alarm System Control Panel). 

 

Example: Rearming the reader by using a TOGGLE User card 

 

Read your TOGGLE User card; once the card is accepted the reader grants you access and its LED 

SYSTEM starts blinking. 

 

With the LED SYSTEM blinking, present your TOGGLE card one more time. This makes the reader change 

its arming mode (watch for the LED STATUS to change color). 

Note: With the 

Access Disabled When Reader Armed

 option activated and the reader in ARMED mode, to 

gain access first switch the reader to DISARMED mode (use TOGGLE or TOGGLE LTD. card) and then use valid 

card to release the door. 

4.4

 

Unlocking Door 

In order to unlock the door a user is required to present his card to the PRT62 reader. Whenever this happens 

the reader activates its LED SYSTEM (orange) for a moment and generates a short confirmation beep. After 

successful identification the reader energizes the door lock for the predefined time (see section 5.3 Installer 

Programming Mode for information on C1C2 

Door Lock Triggering Time control parameters

). The lock 

activation is signaled on LED OPEN (green), which remains ON for as long as the door lock is energized. When 

access to the supervised room is denied the reader generates a long beep. The access to a room can be 

rejected in the following situations: 

 

When the presented card is not valid (unknown); 

 

When the presented card belongs to a TOGGLE LTD class user; 

 

When the reader operates in ARMED mode and the 

Access Disabled When Reader Armed

 option is 

active. 

In the last case the TOGGLE or TOGGLE LTD. can read its card in order to switch the reader from ARMED to 

DISARMED mode, thus re-enabling the reader to grant access to other users.  

Содержание PRT62

Страница 1: ...Installation and Programming Guide PRT62 v1 1 Outdoor Access Control Terminal Firmware v74 7 ...

Страница 2: ...nd alone Operation Mode 5 3 2 2 Simple Stand alone Mode 6 4 Stand alone Operation 6 4 1 Users 6 4 2 ARMED and DISARMED Modes 6 4 3 Arming and Disarming of the Reader Reader Rearming 7 4 4 Unlocking Door 7 4 5 Alarms 8 4 6 Acoustic and Optical Signals 9 5 Programming 10 5 1 Setting Reader Operating Mode 10 5 2 Memory Reset Procedure Programming MASTER and INSTALLER cards 11 5 2 1 Factory Default Se...

Страница 3: ... outputs the other uses them for communication with an external XM 2 I O module and a second PRT series reader An access control installation containing two PRT series readers one at the entry the other at the exit side of the supervised door enables two way passage control The system setup utilizing an XM 2 module provides higher level of security for door access control system by separating its ...

Страница 4: ...vailable in the selected data transmission format a PRT reader omits the most significant bits of the data transmitted As a result you may observe that the actual card codes send by the reader differs from the full card code When Wiegand format is used the dual color LED STATUS indicator lights steady in RED and the LED SYSTEM turns ON for a short while with each reading of a card The LED OPEN is ...

Страница 5: ... Operation Mode In this mode the reader s CLK and DTA lines are used for communication with a remote XM 2 I O module and optionally with an additional secondary PRT series reader for two way door control The IN1 line operates as an input and can be configured to various options The I O lines on the XM 2 module can be programmed to have several predefined functions see settings for C5 C6 C7 C8 and ...

Страница 6: ...e authorized to change ARMED DISARMED mode of the reader only they are not authorized for door unlocking A new user can be registered in the reader following either a simple or a full programming procedure The simple procedure consists in programming a card into the system without specifying the ID number of the user to whom the programmed card will belong as a result the system simply stores the ...

Страница 7: ...ng user requests only if the input line receives an active signal Consequently when Ready Input is not triggered passive state the PRT6t2 will reject any attempt to arm the reader Typically the reader s Ready Input line should be wired to the Alarm System Control Unit s output designed to indicate that the Alarm System is ready for arming Ready Output on an Alarm System Control Panel Example Rearm...

Страница 8: ...gered the reader indicates the alarm with the highest priority The Forced Entry and the Door Ajar alarms will occur only if the reader operates with a Door Open Contact Alarm Signaling Methods Alarm type Priority Signaling method Alarm situation event Forced Door High By cycles with the following sequence Active 4 sec Pause 4 sec The door opened without use of a valid card Prealarm Medium By cycle...

Страница 9: ...ong audible signal one short audible signal beep LED Indications in Stand alone Operation Mode LED STATUS LED OPEN LED SYSTEM Description Green The reader is in DISARMED state now Red The reader is in ARMED state now Red Green The reader is in User Programming Mode Green Green The reader is in Installer Programming Mode Orange flashing Waiting for the user to enter the next part of the command or ...

Страница 10: ...and special marks and and so to simulate a N digit read your Programming Card N times simply present it to the reader and take it back and then wait 2 3 seconds for the reader to generate a special acoustic signal this is a prompt indicating that the reader has successfully accepted the series of your card readings as an entry of a single digit or mark and is now ready for the next step of the pro...

Страница 11: ...er all MASTER and INSTALLER card information as well as all programmed users it clears all cards Also it causes the reader to restore factory default settings The Memory Reset execution is required only if the unit is configured for stand alone mode It does not affect the unit that is configured for host controlled ONLINE mode To clear the reader s memory follow these steps Power down the unit Rem...

Страница 12: ...der Door Contact Input program C7 1 Line IN1 on the XM 2 module Exit Button Input program C8 2 Line IN2 on the XM 2 module Ready Input program C9 3 Option Door Alarm Indication On Internal Buzzer Option enabled program C10 1 Option Access Disabled When Reader Armed Option enabled program C11 1 In order to configure the reader to use the set of options listed above you have to perform the following...

Страница 13: ...al output is modulated according to the detected alarm type If more then one alarm has been triggered the output signals the one of the highest priority C6 0 7 Function settings for the REL2 output on the XM 2 module or for the reader s DTA line assignments as in C5 C7 0 3 Function settings for the reader s IN1 line 0 Not Used 1 Door Contact Input 2 Exit Button Input 3 Ready Input C8 0 3 Function ...

Страница 14: ...c prompt to let you know it is ready to read the next one This function will be ended automatically if no card is presented within 20 sec from the last completed card presentation or you can end it manually by entering a mark Note that the new card users added with this function are stored in unoccupied free locations of the memory and their IDs are unknown 6 ID Card Add one TOGGLE type user with ...

Страница 15: ...tallations on a metal surface place a non metallic min 10 mm thick spacer a plastic plaster plate etc between the reader and the supporting structure For installations with two readers to be mounted on opposite sides of the same wall and aligned along the same geometrical axis place a metal plate between them and make sure none of them has direct contact with it allow min 10 mm space For best resu...

Страница 16: ...IEGAND Communication Interface 70 ONLINE Mode 66 bit WIEGAND Communication Interface The reader operates as a unit controlled by a host This host controlled mode requires the reader to be wired to a master ACU that requires 26 34 42 66 bit Wiegand data format Note For details how to select the required Reader Operating Mode see section 5 1 Offline mode Wire Color Label Simple Stand alone mode Full...

Страница 17: ... 2 Relay module the RM 2 offers two relays with one NO NC contact 5A 24V rated relay contacts are protected with overvolatge elements XM 2 I O extension module digital communication with host reader two NO NC inputs and two relay outputs each relay offers one NO NC contact 5A 24V rated Relay contacts are protected with overvoltage elements Product History Hardware Firmware Date Description PRT62 v...

Страница 18: ...0 25 2007 18 LIST OF USERS Site name Reader location ID Number Card number PIN Type User Name Master Installer Contact information Roger sp j 82 416 Gościszewo Gościszewo 59 Phone 055 272 0132 Fax 055 272 0133 e mail biuro roger pl ...

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ... This page intentionally left blank ...

Страница 28: ......

Страница 29: ...solve the problem They may be reached at 48 55 2670126 or support roger pl Monday through Friday 8 00 A M to 4 00 P M GMT 1 You can also contact the Technical Support Department by fax at 48 55 2720133 If it is determined that you need to return the product the following procedure must be followed to ensure prompt service ROGER Sp j Gosciszewo 59 82 416 Gosciszewo pomorskie Poland Tel 48 55 272 01...

Страница 30: ... form in order to avoid damages during transit You are advised to get proof of delivery 12 Some repairs may be chargeable and you will receive formal advice if this is the case 13 If product returned as defective is found not to be defective it will be returned back to the customer at his expenses In that case the customer will be also charged with costs which may arise after triggering the RMA pr...

Страница 31: ...Notes No Fault description filled out by the customer Date of repair filled out by the service 1 2 3 4 5 ...

Страница 32: ...due to the continual development of new techniques for intruding upon and attacking networks Roger does not warrant that the Product will be free of vulnerability to intrusion or attack This warranty does not cover repair or replacement where normal use has exhausted the life of a part or instrument ALL IMPLIED WARRANTIES AND CONDITIONS OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE LI...

Отзывы: