PRT62 v1.1 fv74 EN Rev.E.DOC 

 

 

 

 

 

 

 

10/25/2007 

 

 

15 

 

 

 

 

 

Wait for the acoustic prompt. 

 

Present 5 times your Programming Card to the reader. 

 

 

(this is to emulate [5]) 

 

Wait for the acoustic prompt. 

 

Present a card intended for the new user. 

 

Present 12 times your Programming Card to the reader.  

 

 

(this is to emulate [#]) 

 

Wait for the acoustic prompt. 

 

Now the user programming sequence is completed. 

The reader has registered the new user card in its memory and exited the programming function, however, it 

has not left User Programming Mode so that now you may use your next desired programming command or 

you may leave this programming mode.  

 

Example 2: Delete a user by using his ID=45  

Programming sequence: [9][4][5][#] 

 

Read your MASTER card, the reader enters User Programming Mode (LED OPEN is ON and LED STATUS 

is ON and RED). 

 

Present 9 times your Programming Card to the reader.  

 

 

(this is to emulate [9]) 

 

Wait for the acoustic prompt. 

 

Present 4 times your Programming Card to the reader.  

 

 

(this is to emulate [4]) 

 

Wait for the prompt acoustic signal. 

 

Present 5 times your Programming Card to the reader.  

 

 

(this is to emulate [5]) 

 

Wait for the acoustic prompt. 

 

Present 12 times your Programming Card to the reader.  

 

 

(this is to emulate [#]) 

 

Wait for the acoustic prompt. 

 

This ends the command. 

The reader deletes the user with ID=45 from its memory, however, it remains in User Programming Mode, so 

that you may use your next desired programming command or you may leave this programming mode. 

 

 

6

 

I

N S T A L L A T I O N   A N D  

S

E T U P    

G

U I D E L I N E S

 

 

The PRT62 reader should be mounted near the supervised door on a vertical piece of supporting 

structure. 

 

Disconnect power supply before making any electrical connections. 

 

For installations on a metal surface, place a non-metallic min. 10 mm thick spacer (a plastic/plaster 

plate etc.) between the reader and the supporting structure. 

 

For installations with two readers to be mounted on opposite sides of the same wall and aligned along 

the same geometrical axis, place a metal plate between them and make sure none of them has direct 

contact with it (allow min. 10 mm space ). 

 

For best results mount the proximity readers at least 0.5 m apart. 

 

When using separate power supply sources, connect all power supply negative (–) leads together. 

 

Roger recommends to ground the negative (–) power supply lead. 

 

With its relatively weak electromagnetic field generation, the terminal should not cause any harmful 

interferences to operation of other equipment. However, its card reading performance can be affected by 

other interference generating devices, esp. radio waves emitting equipment or CRT computer monitors. 

 

If card reading performance of the reader deteriorates (e.g. reduced reading range or incorrect 

readings) consider reinstallation in a new location. 

 

Once installed and electrically connected, the reader has to be properly configured. For this you need  

programming cards: MASTER card and INSTALLER card, and the unit has to be in programming mode. A 

new factory delivered unit is preprogrammed for Online RACS mode with ID0 device address.  

 

Any EM 125 kHz card can be programmed as a MASTER or an INSTALLER card, Roger Sp.J. does not 

supply the reader with any cards. 

 

When lost, MASTER or INSTALLER cards can be reprogrammed to a reader. 

 

The Reader Operating mode

 

can be changed whenever required. 

When the reader has been set for ONLINE operation, the programming of MASTER and INSTALLER cards can be 

skipped. 

 

7

 

A

P P E N D I X

 

 

Reader Operating Modes – Programming Codes 

Code 

Operating Mode 

Description 

06 

OFFLINE Mode 

The reader operates as a stand-alone unit, its CLK and 

Содержание PRT62

Страница 1: ...Installation and Programming Guide PRT62 v1 1 Outdoor Access Control Terminal Firmware v74 7 ...

Страница 2: ...nd alone Operation Mode 5 3 2 2 Simple Stand alone Mode 6 4 Stand alone Operation 6 4 1 Users 6 4 2 ARMED and DISARMED Modes 6 4 3 Arming and Disarming of the Reader Reader Rearming 7 4 4 Unlocking Door 7 4 5 Alarms 8 4 6 Acoustic and Optical Signals 9 5 Programming 10 5 1 Setting Reader Operating Mode 10 5 2 Memory Reset Procedure Programming MASTER and INSTALLER cards 11 5 2 1 Factory Default Se...

Страница 3: ... outputs the other uses them for communication with an external XM 2 I O module and a second PRT series reader An access control installation containing two PRT series readers one at the entry the other at the exit side of the supervised door enables two way passage control The system setup utilizing an XM 2 module provides higher level of security for door access control system by separating its ...

Страница 4: ...vailable in the selected data transmission format a PRT reader omits the most significant bits of the data transmitted As a result you may observe that the actual card codes send by the reader differs from the full card code When Wiegand format is used the dual color LED STATUS indicator lights steady in RED and the LED SYSTEM turns ON for a short while with each reading of a card The LED OPEN is ...

Страница 5: ... Operation Mode In this mode the reader s CLK and DTA lines are used for communication with a remote XM 2 I O module and optionally with an additional secondary PRT series reader for two way door control The IN1 line operates as an input and can be configured to various options The I O lines on the XM 2 module can be programmed to have several predefined functions see settings for C5 C6 C7 C8 and ...

Страница 6: ...e authorized to change ARMED DISARMED mode of the reader only they are not authorized for door unlocking A new user can be registered in the reader following either a simple or a full programming procedure The simple procedure consists in programming a card into the system without specifying the ID number of the user to whom the programmed card will belong as a result the system simply stores the ...

Страница 7: ...ng user requests only if the input line receives an active signal Consequently when Ready Input is not triggered passive state the PRT6t2 will reject any attempt to arm the reader Typically the reader s Ready Input line should be wired to the Alarm System Control Unit s output designed to indicate that the Alarm System is ready for arming Ready Output on an Alarm System Control Panel Example Rearm...

Страница 8: ...gered the reader indicates the alarm with the highest priority The Forced Entry and the Door Ajar alarms will occur only if the reader operates with a Door Open Contact Alarm Signaling Methods Alarm type Priority Signaling method Alarm situation event Forced Door High By cycles with the following sequence Active 4 sec Pause 4 sec The door opened without use of a valid card Prealarm Medium By cycle...

Страница 9: ...ong audible signal one short audible signal beep LED Indications in Stand alone Operation Mode LED STATUS LED OPEN LED SYSTEM Description Green The reader is in DISARMED state now Red The reader is in ARMED state now Red Green The reader is in User Programming Mode Green Green The reader is in Installer Programming Mode Orange flashing Waiting for the user to enter the next part of the command or ...

Страница 10: ...and special marks and and so to simulate a N digit read your Programming Card N times simply present it to the reader and take it back and then wait 2 3 seconds for the reader to generate a special acoustic signal this is a prompt indicating that the reader has successfully accepted the series of your card readings as an entry of a single digit or mark and is now ready for the next step of the pro...

Страница 11: ...er all MASTER and INSTALLER card information as well as all programmed users it clears all cards Also it causes the reader to restore factory default settings The Memory Reset execution is required only if the unit is configured for stand alone mode It does not affect the unit that is configured for host controlled ONLINE mode To clear the reader s memory follow these steps Power down the unit Rem...

Страница 12: ...der Door Contact Input program C7 1 Line IN1 on the XM 2 module Exit Button Input program C8 2 Line IN2 on the XM 2 module Ready Input program C9 3 Option Door Alarm Indication On Internal Buzzer Option enabled program C10 1 Option Access Disabled When Reader Armed Option enabled program C11 1 In order to configure the reader to use the set of options listed above you have to perform the following...

Страница 13: ...al output is modulated according to the detected alarm type If more then one alarm has been triggered the output signals the one of the highest priority C6 0 7 Function settings for the REL2 output on the XM 2 module or for the reader s DTA line assignments as in C5 C7 0 3 Function settings for the reader s IN1 line 0 Not Used 1 Door Contact Input 2 Exit Button Input 3 Ready Input C8 0 3 Function ...

Страница 14: ...c prompt to let you know it is ready to read the next one This function will be ended automatically if no card is presented within 20 sec from the last completed card presentation or you can end it manually by entering a mark Note that the new card users added with this function are stored in unoccupied free locations of the memory and their IDs are unknown 6 ID Card Add one TOGGLE type user with ...

Страница 15: ...tallations on a metal surface place a non metallic min 10 mm thick spacer a plastic plaster plate etc between the reader and the supporting structure For installations with two readers to be mounted on opposite sides of the same wall and aligned along the same geometrical axis place a metal plate between them and make sure none of them has direct contact with it allow min 10 mm space For best resu...

Страница 16: ...IEGAND Communication Interface 70 ONLINE Mode 66 bit WIEGAND Communication Interface The reader operates as a unit controlled by a host This host controlled mode requires the reader to be wired to a master ACU that requires 26 34 42 66 bit Wiegand data format Note For details how to select the required Reader Operating Mode see section 5 1 Offline mode Wire Color Label Simple Stand alone mode Full...

Страница 17: ... 2 Relay module the RM 2 offers two relays with one NO NC contact 5A 24V rated relay contacts are protected with overvolatge elements XM 2 I O extension module digital communication with host reader two NO NC inputs and two relay outputs each relay offers one NO NC contact 5A 24V rated Relay contacts are protected with overvoltage elements Product History Hardware Firmware Date Description PRT62 v...

Страница 18: ...0 25 2007 18 LIST OF USERS Site name Reader location ID Number Card number PIN Type User Name Master Installer Contact information Roger sp j 82 416 Gościszewo Gościszewo 59 Phone 055 272 0132 Fax 055 272 0133 e mail biuro roger pl ...

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ... This page intentionally left blank ...

Страница 28: ......

Страница 29: ...solve the problem They may be reached at 48 55 2670126 or support roger pl Monday through Friday 8 00 A M to 4 00 P M GMT 1 You can also contact the Technical Support Department by fax at 48 55 2720133 If it is determined that you need to return the product the following procedure must be followed to ensure prompt service ROGER Sp j Gosciszewo 59 82 416 Gosciszewo pomorskie Poland Tel 48 55 272 01...

Страница 30: ... form in order to avoid damages during transit You are advised to get proof of delivery 12 Some repairs may be chargeable and you will receive formal advice if this is the case 13 If product returned as defective is found not to be defective it will be returned back to the customer at his expenses In that case the customer will be also charged with costs which may arise after triggering the RMA pr...

Страница 31: ...Notes No Fault description filled out by the customer Date of repair filled out by the service 1 2 3 4 5 ...

Страница 32: ...due to the continual development of new techniques for intruding upon and attacking networks Roger does not warrant that the Product will be free of vulnerability to intrusion or attack This warranty does not cover repair or replacement where normal use has exhausted the life of a part or instrument ALL IMPLIED WARRANTIES AND CONDITIONS OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE LI...

Отзывы: