PRT-EM Series Readers fv 1.29 and 2.29 Rev. J.doc
2012-01-05
Page 18 from 59
5.7.
D
OOR
A
LARM
The
Door Alarm
is a compound state which consists of one or more situations which are related to
controlled door passage:
Forced Entry
Prealarm
Door Ajar
The
Door Alarm
state can be signaled over the dedicated output
[46]: Door Alarm
and
optionally on the internal buzzer (option:
Door Alarm indication on internal buzzer
). For
indication of each particular type of alarm reader uses different signal modulation.
Note: The
Forced Entry
and
Door Ajar
alarms can occur only if the reader operates with a door
open sensor (
[21]: Door Contact
input must be present).
5.8.
T
AMPER
A
LARM
This alarm is dedicated to indicate that reader’s case is open or reader is detached from the place
of installation.
Tamper Alarm
can arise either in armed or disarmed mode and is caused by active
state on
[26]: Tamper
input. Once this alarm emerges reader starts counting
Tamper Timer
and
activates outputs:
[55]: Tamper Alarm
and/or
[57]: General Alarm
(if programmed). During
time period when
Tamper Timer
counts down reader disables
[26]: Tamper
input thus
protecting the reader from multiply tamper alarms. The
Tamper Alarm
ceases automatically when
Tamper Timer
reaches the end or reader changes its arming mode.
5.9.
I
NTRUDER
A
LARM
This alarm is dedicated to indicate that some intruder is penetrating area protected with sensor
connected to reader’s input
[27]: Intruder
or door was opened in unauthorized method (
Forced
Door Alarm
Event
Priority
Output modulation method
Alarm situation
Forced
Entry
High
Sequence:
Active - 4 sec., Pause - 4 sec.
A door was open in
unauthorized method. This
state can be cleared by
entering any valid identifier or
disappears automatically after
3 minutes.
Prealarm
Medium
Sequence:
Active - 1 sec., Pause - 1 sec.
Detection of five consecutive
usage of unknown card/PIN
made within 5 minutes.
Entering valid card/PIN clears
fault attempt counter. During
Prealarm state reader
disables reading of cards and
PIN-s thus blocking the users’
identification for 5 minutes.
Door Ajar
Low
Sequence:
Active - 1 sec., Pause - 1 sec., Active -
1 sec., Pause - 5 sec.
Door not closed within
Door
Open Timeout
. This state
can be cleared by entering
any valid identifier or
disappears automatically after
3 minutes. Also, closing door
immediately clears this alarm.
Note: Modulation methods are used for both, the output line and for internal buzzer as well (if
configured for alarm indication).
Содержание PRT12EM
Страница 43: ...PRT EM Series Readers fv 1 29 and 2 29 Rev J doc 2012 01 05 Page 43 from 59...
Страница 50: ...PRT EM Series Readers fv 1 29 and 2 29 Rev J doc 2012 01 05 Page 50 from 59...
Страница 51: ...PRT EM Series Readers fv 1 29 and 2 29 Rev J doc 2012 01 05 Page 51 from 59...
Страница 52: ...PRT EM Series Readers fv 1 29 and 2 29 Rev J doc 2012 01 05 Page 52 from 59...
Страница 53: ...PRT EM Series Readers fv 1 29 and 2 29 Rev J doc 2012 01 05 Page 53 from 59...
Страница 54: ...PRT EM Series Readers fv 1 29 and 2 29 Rev J doc 2012 01 05 Page 54 from 59...
Страница 55: ...PRT EM Series Readers fv 1 29 and 2 29 Rev J doc 2012 01 05 Page 55 from 59...
Страница 56: ...PRT EM Series Readers fv 1 29 and 2 29 Rev J doc 2012 01 05 Page 56 from 59...
Страница 57: ...PRT EM Series Readers fv 1 29 and 2 29 Rev J doc 2012 01 05 Page 57 from 59...
Страница 58: ...PRT EM Series Readers fv 1 29 and 2 29 Rev J doc 2012 01 05 Page 58 from 59...