background image

PR611 and PR621 Installation guide Rev.B EN 

2009-11-06 

 

 
Page 

3

 of 

13

 

Presence of two or more devices having the same address causes the communication bus conflict 
and makes a proper communication with the device impossible. 

Note: A new controller can be connected to the existing system without the necessity to change its 

address, however only under condition that no controller existing in the system has the address 
identical to the address of the newly connected device (e.g. 00). After the controller is connected to 

the communication bus, it should be found in the management software and the destination address 
should be assigned to it. 

Power Supply 

The controller requires 12V DC nominal power supply.  The power should be connected to the +12V 
line (positive terminal) and the GND (negative terminal). Apart from powering function, the GND 

terminal plays also the role as reference potential for the RS485 bus’ communication lines, IN1-IN3 
inputs and CLK/DTA interface lines. 

Connecting Door Unlocking Device 

In majority of cases, door unlocking devices have inductive characteristics. It means that turning off 
the current flowing through the device may cause the electrical overvoltage condition which can 
interfere with the controller operation. In extreme cases it may lead to the controller’s hanging up. 

Moreover, the presence of overvoltages causes quicker attrition of the relay’s contacts. In order to 
limit negative impact of overvoltages, it is necessary to utilize a semiconductor diode of general use 

e.g. 1N4007 (one piece of such diode is delivered with the controller). It should be connected as 
close as possible to the inductive element (electric strike or magnetic lock). The door lock device 

element can be supplied from the same power source as the controller but for such purpose the 
separate pair of wires should be used and connected directly to the power supply’s terminals. 

 

Output Lines 

All the controller’s inputs (IN1, IN2 i IN3) have identical electric structure and can be configured as 
lines of NO or NC type. The NO input is triggered by applying supply minus to it, the NC input must 

be normally shorted to the supply minus (GND) and is triggered by disconnecting it form the minus. 
Every input is internally connected (pulled up) to the power supply plus (+12V) through a 5.6k

 

resistor. 

Relay Outputs 

The relay output REL1 offers one switched contact rated 24V/1.5A. The relay’s contacts are 
internally protected against overvoltages by semiconductor elements. However this does not take 

the responsibility out of the installer to eliminate interferences from inductive elements by an 
additional diode. It is forbidden to use relay output to switch voltages above 30V because this for 

sure will cause damage to the semiconductor elements protecting the relay’s contacts. In the normal 
state (the relay is off) the NC-COM contacts are shorted. In the triggering state (the relay is on) the 

NO-COM contacts are shorted. In case of lack of the power, the REL1 output is in the off state. 

Transistor Outputs 

Содержание PR611

Страница 1: ...Installation Guide for PR611 and PR621 v1 0 Access Controllers Rev B ...

Страница 2: ...the separate wire The other solution is to individually ground connect to earth each of GND terminals However the latter solution is not recommended because when grounding potentials in different locations of installation are not the same the equalizing current will flow through the system s power supply lines That in turn can cause disruption of system work or even its damage Readers can be insta...

Страница 3: ... limit negative impact of overvoltages it is necessary to utilize a semiconductor diode of general use e g 1N4007 one piece of such diode is delivered with the controller It should be connected as close as possible to the inductive element electric strike or magnetic lock The door lock device element can be supplied from the same power source as the controller but for such purpose the separate pai...

Страница 4: ...communication through a computer network LAN or WAN Connecting Readers and Extension Modules The controller can cooperate with one additional reader of PRT series configured to RACS mode with ID0 address It can also cooperate with XM 2 I O extension module Both an additional reader and an extension module can be connected to the controller using the same CLK and DTA lines For CLK and DTA lines any...

Страница 5: ...mming a MASTER card and PIN as well as setting up a new address ID number Remove all connections from CLK and DTA lines Short CLK and DTA lines Restart device switch power supply off and then on or short RST contacts for a while all the LED indicators on the reader will be lit Remove the bridge between CLK and DTA lines the LEDs on the reader will be off and the LED OPEN green will start flashing ...

Страница 6: ...is the software used for upgrading firmware it can be downloaded at www roger pl After the firmware is upgraded always perform the Memory Reset procedure and assign a proper ID address to the controller If the controller being upgraded worked in the RACS system before you need to assign to it appropriate ID address after the upgrade the same which it was assigned before the upgrade Then you need t...

Страница 7: ...on metallic spacer 10 mm thick at a minimum It is recommended that the reader be installed at a distance not lower than 0 5 m from the other reader All the devices communicating between themselves readers extension modules controllers should have be connected to the same common minus potential Optionally system supply minus can be earthed in one arbitrary selected location Do not connect system su...

Страница 8: ...t line internally connected to the power supply plus through a 5 6kΩ resistor RS485 B 6 Green white RS485 communication bus B line RS485 A 7 Brown RS485 communication bus A line CLK 8 White RACS Clock Data communication interface CLOCK line DTA 9 Green RACS Clock Data communication interface DATA line TMP A 10 Yellow Anti sabotage contact line A rated 24V 50mA TMP B 11 Grey Anti sabotage contact l...

Страница 9: ...cards depends on card type and quality Proximity cards EM 125 KHz EM4100 4102 compatible Distances RS485 comm bus up to 1200m Between an additional reader and the controller max 150 m Between a reader and XM 2 XM 8 expansion modules max 150 m Environmental class according to EN 50131 1 Class IV outdoor general conditions temperature 25 C 60 C relative humidity 10 to 95 Dimensions PR611 115 X 80 X ...

Страница 10: ...The module can be located in a distance of 150 m from the host device controller XM 2 PCB XM 2 PCB module without enclosure UT 2 RS232 RS485 communication interface UT 2USB USB RS485 communication interface RUD 1 USB RS485 communication interface with 12V DC 150mA supply output UT 4 Ethernet RS485 RS232 communication interface Contact Roger sp j 82 416 Gościszewo Gościszewo 59 Tel 48 55 272 01 32 ...

Страница 11: ...PR611 and PR621 Installation guide Rev B EN 2009 11 06 Page 11 of 13 ...

Страница 12: ...PR611 and PR621 Installation guide Rev B EN 2009 11 06 Page 12 of 13 ...

Страница 13: ...PR611 and PR621 Installation guide Rev B EN 2009 11 06 Page 13 of 13 ...

Отзывы: