PR611 and PR621 Installation guide Rev.B EN 

2009-11-06 

 

 
Page 

5

 of 

13

 

Simplified Memory Reset Procedure (version 2) 

This method clears entire memory and allows for programming a MASTER card and allows to set ID 
address. This procedure doesn’t require use of a keypad. 

 

Remove all connections from CLK and IN3 lines 

 

Short CLK and IN3 lines 

 

Restart device (switch power supply off and then on or short RST contacts for a while) – all 
the LED indicators on the reader will be lit 

 

Remove the bridge between CLK and IN3 lines — the LEDs on the reader will be off, and then  
the LED STATUS   and LED OPEN   (green) will start flashing 

 

While the LED OPEN   is flashing, read any card — this will be the new MASTER card then 
move to the next step where you will program controller’s ID number (address) 

 

Read MASTER card X times where X must be equal to the first digit of the required address 

then wait for two short beeps 

 

Read MASTER card Y times where Y must be equal to the second digit of the required address 

 

The reader will restart automatically and return to normal mode of operation 

 
Full Memory Reset Procedure  

This procedure can be performed directly from the controller’s keypad (if the controller has it) or 

from an additional PRT series reader connected to the controller through CLK and DTA lines. The 
reader used for this should be configured to the 

RACS mode address ID0

 and be equipped with a 

keypad. Full Memory Reset procedure clears entire memory and allows for programming a MASTER 
card and PIN as well as setting up a new address (ID number). 

 

Remove all connections from CLK and DTA lines. 

 

Short CLK and DTA lines. 

 

Restart device (switch power supply off and then on or short RST contacts for a while) – all 
the LED indicators on the reader will be lit. 

 

Remove the bridge between CLK and DTA lines — the LEDs on the reader will be off, and the 
LED OPEN   (green) will start flashing. 

 

If the controller is equipped with keypad go to the next step if not then without switching the 

power off connect an external PRT series reader to it. It should be configured to the RACS 
mode address=ID0. The rest of the steps should be performed using this additional reader. 

 

Enter a new MASTER PIN code (3-6 digits) followed with the [#] key or skip this step 

pressing the [#] key alone. 

 

Read any card — it will be a new MASTER card — or skip this step by pressing the [#] key. 

 

Enter two digits (from 00 to 99 range). These digits program a new ID address of the 
controller. Eventually, instead of programming controller’s address can press the [#] key 

alone. In the latter case, the controller will automatically assume address ID=00. 

 

After this action, the reader will restart automatically and return to normal working mode 
(enters Armed mode). 

 
After 

Memory Reset

 procedure, controller resumes its work with default configuration settings. You 

can then initially test its operation using a MASTER ID card or PIN (if they were programmed). Using 
the MASTER card or PIN once, activates a relay output REL1 for 4 seconds  and LED OPEN    in on 
along with REL1. Using it twice switches the IO1 output to the opposite state, and changes a current 

controller’s armed mode (LED STATUS   changes its color). 

Содержание PR611

Страница 1: ...Installation Guide for PR611 and PR621 v1 0 Access Controllers Rev B ...

Страница 2: ...the separate wire The other solution is to individually ground connect to earth each of GND terminals However the latter solution is not recommended because when grounding potentials in different locations of installation are not the same the equalizing current will flow through the system s power supply lines That in turn can cause disruption of system work or even its damage Readers can be insta...

Страница 3: ... limit negative impact of overvoltages it is necessary to utilize a semiconductor diode of general use e g 1N4007 one piece of such diode is delivered with the controller It should be connected as close as possible to the inductive element electric strike or magnetic lock The door lock device element can be supplied from the same power source as the controller but for such purpose the separate pai...

Страница 4: ...communication through a computer network LAN or WAN Connecting Readers and Extension Modules The controller can cooperate with one additional reader of PRT series configured to RACS mode with ID0 address It can also cooperate with XM 2 I O extension module Both an additional reader and an extension module can be connected to the controller using the same CLK and DTA lines For CLK and DTA lines any...

Страница 5: ...mming a MASTER card and PIN as well as setting up a new address ID number Remove all connections from CLK and DTA lines Short CLK and DTA lines Restart device switch power supply off and then on or short RST contacts for a while all the LED indicators on the reader will be lit Remove the bridge between CLK and DTA lines the LEDs on the reader will be off and the LED OPEN green will start flashing ...

Страница 6: ...is the software used for upgrading firmware it can be downloaded at www roger pl After the firmware is upgraded always perform the Memory Reset procedure and assign a proper ID address to the controller If the controller being upgraded worked in the RACS system before you need to assign to it appropriate ID address after the upgrade the same which it was assigned before the upgrade Then you need t...

Страница 7: ...on metallic spacer 10 mm thick at a minimum It is recommended that the reader be installed at a distance not lower than 0 5 m from the other reader All the devices communicating between themselves readers extension modules controllers should have be connected to the same common minus potential Optionally system supply minus can be earthed in one arbitrary selected location Do not connect system su...

Страница 8: ...t line internally connected to the power supply plus through a 5 6kΩ resistor RS485 B 6 Green white RS485 communication bus B line RS485 A 7 Brown RS485 communication bus A line CLK 8 White RACS Clock Data communication interface CLOCK line DTA 9 Green RACS Clock Data communication interface DATA line TMP A 10 Yellow Anti sabotage contact line A rated 24V 50mA TMP B 11 Grey Anti sabotage contact l...

Страница 9: ...cards depends on card type and quality Proximity cards EM 125 KHz EM4100 4102 compatible Distances RS485 comm bus up to 1200m Between an additional reader and the controller max 150 m Between a reader and XM 2 XM 8 expansion modules max 150 m Environmental class according to EN 50131 1 Class IV outdoor general conditions temperature 25 C 60 C relative humidity 10 to 95 Dimensions PR611 115 X 80 X ...

Страница 10: ...The module can be located in a distance of 150 m from the host device controller XM 2 PCB XM 2 PCB module without enclosure UT 2 RS232 RS485 communication interface UT 2USB USB RS485 communication interface RUD 1 USB RS485 communication interface with 12V DC 150mA supply output UT 4 Ethernet RS485 RS232 communication interface Contact Roger sp j 82 416 Gościszewo Gościszewo 59 Tel 48 55 272 01 32 ...

Страница 11: ...PR611 and PR621 Installation guide Rev B EN 2009 11 06 Page 11 of 13 ...

Страница 12: ...PR611 and PR621 Installation guide Rev B EN 2009 11 06 Page 12 of 13 ...

Страница 13: ...PR611 and PR621 Installation guide Rev B EN 2009 11 06 Page 13 of 13 ...

Отзывы: