MCX402DR Operating Manual.doc 

  

2018-09-03 

 

8/11 

 

REL1,REL2 

Parameter defines the polarity of output line. Output with normal 
polarity represents high impedance in normal state and is shorted 
to ground when triggered. Output with reversed polarity operates 
with inverted logic. It is shorted to ground in normal state and 
represents high impedance when triggered. Range: [0]: Normal 
polarity, [1]: Reversed polarity. Default value: 0 

IO1, IO2 

as above 

Output and power supply comments 

REL1, REL2 

Parameter defines any text or comment which corresponds to the 
object. It is later displayed in VISO program. 

IO1,IO2 

as above 

PWR 

as above 

Device comment 

DEV 

as above 

Wiegand Terminal 1/2* 

Terminal enabled 

When option is enabled then Wiegand Terminal 1/2 is operated. 
Range: Yes, No. Default value: Yes. 

Keypad enabled 

When option is enabled the keypad on Wiegand Terminal 1/2 is 
operated. Range: Yes, No. Default value: Yes. 

Card type 

Parameter defines the data type of the card returned by terminal. 
Default value: [16]: Number 40bits.  

Card class 

Parameter defines the class of the card returned by terminal. 
Default value: [2]: EM. 

KBD comment 

Parameter defines any text or comment which corresponds to the 
object. It is later displayed in VISO program. 

CDI comment 

as above 

Card code length 

Parameter defines type of Wiegand 26-66bit interface. Range: 0-
66. Default value: 26 

Card code reverse order 

When the option is enabled then expected card code returned by 
terminals is in reverse order. Range: Yes, No. Default value: No. 

PIN format 

Parameter defines format of PIN returned by terminal. Range: [0]: 
None, [1]: BIN, [2]: BCD, [3]: HEX. Default value: [0]: None. 

PIN length 

Parameter defines the length of PIN returned by terminal. Range: 
0-64. Default value: 0. 

PIN reverse order 

When option is enabled then expected PIN returned by terminal is 
in reverse order. Range: Yes, No. Default value: No. 

Single key press 

When option is enabled then reader transmits the whole PIN to 
controller. When option is disabled then reader transmits every 
pressed key separately. Range: Yes, No. Default value: No. 

Terminal RACS CLK/DTA ID0/ID1** 

Terminal enabled 

When option is enabled then PRT terminal ID0/ID1 on RACS 
CLK/DTA bus is operated. Range: Yes, No. Default value: Yes. 

Keypad enabled 

When option is enabled then keypad on Terminal ID0/ID1 is 
operated. Range: Yes, No. Default value: Yes. 

Card type 

Parameter defines the data type of the card returned by terminal. 
Default value: [16]: Number 40bits. 

Содержание MCX402DR-BRD

Страница 1: ...Roger Access Control System MCX402DR BRD I O expander Operating Manual Product version 1 0 Firmware version 1 0 2 255 Document version Rev B...

Страница 2: ...ery The expander is offered individually as electronic module or as a component of MCX402 1 KIT for read in out door control or as a component of MCX402 2 KIT for two read in doors control In case of...

Страница 3: ...from 230VAC 18VAC 40VA transformer and then it offers 13 8VDC power outputs AUX TML for external devices Optionally the expander can be supplied from 12VDC or 24VDC but in case of 12VDC the backup ba...

Страница 4: ...mal state and is shorted to ground when triggered Output with reversed polarity operates with inverted logic It is shorted to ground in normal state and represents high impedance when triggered The co...

Страница 5: ...ad in read out door with PRT readers A and Wiegand readers B Connection of expander to controller The expander is not operated as standalone device but as an extension of MC16 access controller It is...

Страница 6: ...erVDM software address The factory new expander has ID 100 software address Addressing with jumpers Every time the address is modified the expander must be restarted with RST button or switching power...

Страница 7: ...its every pressed key separately Range Yes No Default value Yes Min PIN length Parameter defines minimal number of digits in PIN Range 0 8 When set to 0 then PIN is disabled Default value 4 Max PIN le...

Страница 8: ...ment Parameter defines any text or comment which corresponds to the object It is later displayed in VISO program CDI comment as above Card code length Parameter defines type of Wiegand 26 66bit interf...

Страница 9: ...RT readers then another firmware must be uploaded Such firmware is available at www roger pl Firmware update is also used in case of migration from RACS 4 to RACS 5 when PR411 and PR402 controllers ar...

Страница 10: ...ne CLK GND Ground DTA RACS CLK DTA interface line DTA IN3 IN3 input line GND Ground IN4 IN4 input line A RS485 communication bus line A TML Power supply output 12VDC 0 2A B RS485 communication bus lin...

Страница 11: ...RD I O expander for door control with Wiegand or PRT readers MCX402 1 KIT 1 door expander kit MCX402 2 KIT 2 door expander kit Product history Version Date Description MCX402DR v1 0 10 2017 The first...

Отзывы: