MCX402DR Operating Manual.doc 

  

2018-09-03 

 

3/11 

 

 

Fig. 2 MCX402DR-BRD application in single read-in/out door control (A) and two read-in doors control (B) 

Power supply and backup battery 

MCX402DR-BRD expander is designed for power supply from 230VAC/18VAC/40VA transformer and then 
it offers 13.8VDC power outputs (AUX, TML) for external devices. Optionally the expander can be supplied 
from 12VDC or 24VDC but in case of 12VDC the backup battery cannot be directly connected to the 
expander thus the emergency power supply must be provided by external PSU. 

Note: Expander cannot be started using only power supply from backup battery. 

 

Fig. 3 MCX402DR-BRD supply from 18VAC 
 

Содержание MCX402DR-BRD

Страница 1: ...Roger Access Control System MCX402DR BRD I O expander Operating Manual Product version 1 0 Firmware version 1 0 2 255 Document version Rev B...

Страница 2: ...ery The expander is offered individually as electronic module or as a component of MCX402 1 KIT for read in out door control or as a component of MCX402 2 KIT for two read in doors control In case of...

Страница 3: ...from 230VAC 18VAC 40VA transformer and then it offers 13 8VDC power outputs AUX TML for external devices Optionally the expander can be supplied from 12VDC or 24VDC but in case of 12VDC the backup ba...

Страница 4: ...mal state and is shorted to ground when triggered Output with reversed polarity operates with inverted logic It is shorted to ground in normal state and represents high impedance when triggered The co...

Страница 5: ...ad in read out door with PRT readers A and Wiegand readers B Connection of expander to controller The expander is not operated as standalone device but as an extension of MC16 access controller It is...

Страница 6: ...erVDM software address The factory new expander has ID 100 software address Addressing with jumpers Every time the address is modified the expander must be restarted with RST button or switching power...

Страница 7: ...its every pressed key separately Range Yes No Default value Yes Min PIN length Parameter defines minimal number of digits in PIN Range 0 8 When set to 0 then PIN is disabled Default value 4 Max PIN le...

Страница 8: ...ment Parameter defines any text or comment which corresponds to the object It is later displayed in VISO program CDI comment as above Card code length Parameter defines type of Wiegand 26 66bit interf...

Страница 9: ...RT readers then another firmware must be uploaded Such firmware is available at www roger pl Firmware update is also used in case of migration from RACS 4 to RACS 5 when PR411 and PR402 controllers ar...