MCX402DR Operating Manual.doc 

  

2018-09-03 

 

4/11 

 

 

Fig. 4 MCX402DR-BRD supply from 12VDC or 24VDC 

Connection to RS485 communication bus 

MCX402DR-BRD is an addressable device and it must be connected to RS485 communication bus of the 
controller where MCT readers and other MCX expanders are usually also operated. Prior to connection, the 
expander must be assigned unoccupied address in range of 100-115. Any topology of communication bus 
can be used (e.g. star, tree). The matching resistors (terminators) connected at the ends of transmitting 
lines are not required. In most cases communication works with any signal cable e.g. U/UTP cat.5. All 
devices connected to the same bus should have GND terminals connected. The RS485 communication 
standard in RACS 5 system guarantees proper communication in a distance of up to 1200 meters as well as 
high resistance to interferences.  

IN1-IN8 inputs 

The expander offers 8 inputs IN1-IN8 which can be configured as NO or NC. Electric parameters of all 
inputs are configured within low level configuration by means of RogerVDM software. Inputs are assigned 
with functions using VISO management software. 

IO1 and IO2 outputs 

The expander offers two open collector type transistor outputs IO1 and IO2. Output polarity can be 
configured as normal or reversed. Output with normal polarity represents high impedance in normal state 
and is shorted to ground when triggered. Output with reversed polarity operates with inverted logic. It is 
shorted to ground in normal state and represents high impedance when triggered. The configuration of 
output polarity is done within low level configuration using RogerVDM software. By default, outputs are 
configured with normal polarity. Outputs are assigned with functions using VISO management software. 

REL1 and REL2 outputs 

The expander offers two relay outputs REL1 and REL2. Each relay offers NO/NC terminals and REL1 is 
30V/1.5A rated while REL2 is 230VAC/5A rated. In case of power outage both relays remain in the off state. 
Outputs are assigned with functions using VISO management software. 

AUX power output 

AUX power supply output is dedicated to supply door lock, alarm signalling device and other door related 
devices. The terminal AUX is protected with 1.0A electronic fuse. 

TML power output 

TML power supply output is dedicated to supply readers at doors. The terminal TML+ is protected with 0.2A 
electronic fuse. 

Door control 

The expander offers power supply at door and enables the operation of PRT (RACS CLK/DTA) or Wiegand 
readers with MC16 access controller. The expander offers 1.0A power output (AUX), 0.2A power output 
(TML), RACS CLK/DTA communication bus and programmable inputs/outputs which can be used to control 
door lock, communication with Wiegand readers and control of LEDs and buzzer of Wiegand readers. The 
1.0A output is dedicated to supply door lock and door related devices (e.g. alarm signalling device). The 

Содержание MCX402DR-BRD

Страница 1: ...Roger Access Control System MCX402DR BRD I O expander Operating Manual Product version 1 0 Firmware version 1 0 2 255 Document version Rev B...

Страница 2: ...ery The expander is offered individually as electronic module or as a component of MCX402 1 KIT for read in out door control or as a component of MCX402 2 KIT for two read in doors control In case of...

Страница 3: ...from 230VAC 18VAC 40VA transformer and then it offers 13 8VDC power outputs AUX TML for external devices Optionally the expander can be supplied from 12VDC or 24VDC but in case of 12VDC the backup ba...

Страница 4: ...mal state and is shorted to ground when triggered Output with reversed polarity operates with inverted logic It is shorted to ground in normal state and represents high impedance when triggered The co...

Страница 5: ...ad in read out door with PRT readers A and Wiegand readers B Connection of expander to controller The expander is not operated as standalone device but as an extension of MC16 access controller It is...

Страница 6: ...erVDM software address The factory new expander has ID 100 software address Addressing with jumpers Every time the address is modified the expander must be restarted with RST button or switching power...

Страница 7: ...its every pressed key separately Range Yes No Default value Yes Min PIN length Parameter defines minimal number of digits in PIN Range 0 8 When set to 0 then PIN is disabled Default value 4 Max PIN le...

Страница 8: ...ment Parameter defines any text or comment which corresponds to the object It is later displayed in VISO program CDI comment as above Card code length Parameter defines type of Wiegand 26 66bit interf...

Страница 9: ...RT readers then another firmware must be uploaded Such firmware is available at www roger pl Firmware update is also used in case of migration from RACS 4 to RACS 5 when PR411 and PR402 controllers ar...

Страница 10: ...ne CLK GND Ground DTA RACS CLK DTA interface line DTA IN3 IN3 input line GND Ground IN4 IN4 input line A RS485 communication bus line A TML Power supply output 12VDC 0 2A B RS485 communication bus lin...

Страница 11: ...RD I O expander for door control with Wiegand or PRT readers MCX402 1 KIT 1 door expander kit MCX402 2 KIT 2 door expander kit Product history Version Date Description MCX402DR v1 0 10 2017 The first...

Отзывы: