HRT82MF Installation Guide Rev.B
2015-08-13
© 2015 ROGER sp.j. All rights reserved.
11/12
5.
T
ROUBLESHOOTING
Table 5. Troubleshooting
Issue
Visual indication
Acoustic
indication
Solution
No
communication
with controller
All LED indicators are
blinking.
-
1. Check if RACS CLK/DTA bus is
properly connected, wires are
undamaged and the bus does
not exceed 150 m. All devices
connected to particular RACS
CLK/DTA bus should have
common supply minus (GND).
2. Check if the controller is
properly configured for
communication with the device.
Device
configuration
error
HOTEL STAFF green
LED indicator single
blinking every 2 sec.
Short beep every
2 sec.
1. Connect the device to PC with
RogerVDM software and
configure it again (see 4.1).
Device firmware
error
HOTEL STAFF green
LED indicator double
blinking every 2 sec.
Short double beep
every 2 sec.
1. Upload the firmware again
(see 4.2)