Table 3 Input functions
No.
Function
Type
Description
[00]
None
-
Input line is not used.
[01]
Clear all alarms
in CPR
ON
monitored
When the input is activated then all alarms are
cleared in CPR32-NET unit.
[02]
Tamper alarm
ON/OFF
monitored
When the input is activated, Tamper alarm is raised
and consequently both, the output with dedicated
function [81] and LED 1 are activated.
[08]
Set all doors to
Normal mode
ON
monitored
When the input is activated then Normal Door
Mode is activated at all controllers (doors) within
subsystem (network).
[09]
Set all doors to
Unlocked mode
ON
monitored
When the input is activated then Unlocked Door
Mode is activated at all controllers (doors) within
subsystem (network).
[10]
Set all doors to
Cond. Unlocked
mode
ON
monitored
When the input is activated then Conditional
Unlocked Door Mode is activated at all controllers
(doors) within subsystem (network).
[11]
Set all doors to
Locked mode
ON
monitored
When the input is activated then Locked Door Mode
is activated at all controllers (doors) within
subsystem (network).
[12]
Clear all alarms
in subsystem
ON
monitored
When the input is activated then all alarms in
CPR32-NET and controllers within particular
subsystem (network) are cleared. The function [12]
operates as a sum of [01] and [13] functions.
[13]
Clear alarms in
all controllers
ON
monitored
When the input is activated then all alarms in
controllers within particular subsystem (network)
are cleared.
[14]
Reset APB
ON
monitored
When the input is activated then APB Register in
subsystem is cleared.
[15]
Set Armed mode
ON
monitored
When the input is activated then all alarm zones in
subsystem and all controllers (doors) not assigned
to alarm zones become armed.
[16]
Set Disarmed
mode
ON
monitored
When the input is activated then all alarm zones in
subsystem and all controllers (doors) not assigned
to alarm zones become disarmed.
[17]
Set all doors to
Unlocked mode
(momentary)
ON/OFF
monitored
As long as the input is activated, Unlocked Door
Mode is activated at all controllers (doors) within
subsystem (network). When the input is
deactivated then Normal Door Mode is restored at
all controller (doors) within subsystem.
Table 5. Output functions
No.
Function
Description
[00]
None
Output line is not used.