background image

CPR32-SE v3.0 User Manual Rev.A.doc

 

2017-04-14 

 

 

12/15 

 

[65] 

External buzzer 

The output is dedicated to connection of external speaker in 
order to signal acoustically following alarms: 

 

firmware  memory  error  –  infinite,  modulated 
signal (3 sec. of sound /3 sec. of pause) 

 

configuration  error  –  repeated  double  short 
acoustic signals 

 

event  memory  error  –  repeated  three  short 
acoustic signals 

 

RTC error – repeated four short acoustic signals 

 

Tamper alarm or Power supply alarm – the signal 
is  modulated  (1  sec.  of  sound/  1  sec.  of  pause) 

and lasts 3 minutes 

[66] 

Data transmitted 

The output is activated whenever data is transmitted by CPR 
on RS485 bus. 

[67] 

Alarm in CPR - 
modulated 

The output is activated for 3 minutes if Tamper Alarm or 

Power supply alarm is raised. The function [67] operates as a 
sum of [81] and [82] functions. The signal is modulated (1 

sec. of signal/ 1 sec. of pause).  

[71] 

Alarm in subsystem 
(network) 

The output is activated for 3 minutes if Tamper Alarm, Power 
supply alarm or any alarm in one of controllers is raised. The 

function [71] operates as a sum of [81], [82] and [72] 
functions. 

[72] 

Alarm in controllers 

The output is activated for 3 minutes if any alarm is raised in 

one of PR series controllers within the subsystem (network). 

[73] 

Alarm in CPR 

The output is activated for 3 minutes if Tamper Alarm or 
Power supply alarm is raised. The function [67] operates as a 

sum of [81] and [82] functions. 

[74] 

Low battery 

The output remains activated as long as charge level of 

backup battery connected to CPR32-NET unit is low. 

[75] 

18VAC supply lost 

The output is activated after 15 minutes of 18VAC power 
supply shortage to CPR32-NET unit and remains activated 

until the power supply is restored. 

[76] 

Battery failure 

The output is activated in case of battery failure (no battery 
or internal damage of battery). If the output is activated then 

the battery must be checked by maintenance personnel. The 
output remains activated until the problem is eliminated. 

[77] 

CPR on 

The output signals that CPR32-NET is switched on by PR 
Master software. 

[78] 

CPR off 

The output signals that CPR32-NET is switched off by PR 
Master software. 

[79] 

Internal failure 

The output is activated when internal testing detects RTC 
failure, firmware memory failure or data memory error. 

Internal test is performed every 20 minutes. The output is 
activated until the failure/error is removed. 

[80] 

Buffer alarm - 
modulated 

The output is activated when the event memory buffer is full 

and remains activated until the buffer is cleared. The signal 
is modulated (1 sec. of signal/ 1 sec. of pause). 

Содержание CPR32-SE v3.0

Страница 1: ...ersion 3 0 5133 or newer Hardware version 3 0 Document version Rev A 2016 ROGER sp z o o sp k All rights reserved This document is subject to the Terms of Use in their current version published at the www roger pl website of the Roger sp z o o sp k company hereinafter referred to as ROGER ...

Страница 2: ...rs 6 3 3 Power supply 6 3 4 Communication with CPR 8 3 5 Input and output lines 8 3 5 1 Inputs 8 3 5 2 Relay outputs 8 3 5 3 General purpose outputs 8 3 6 Installation guidelines 9 4 Configuration 9 4 1 Configuration by means of PR Master software 9 4 2 Memory Reset 13 4 3 Firmware update 13 4 4 Problem with erratic jumps of mouse cursor in Windows OS 14 5 Ordering information 14 6 Product history...

Страница 3: ...erns PRxx1 series controllers The network controller is equipped with RS485 port which is used for direct communication with access controllers and for communication with computer PR Master software using communication interface e g UT 2USB Events from access control system are stored in internal memory buffer max 240 000 events Note The CPR32 NET v3 0 requires PR Master software in version 4 5 20...

Страница 4: ...IN8 input line P2 Power supply for CPR IO1 IO1 output line COM REL1 relay common terminal IO2 IO2 output line NC REL1 relay output NC IN1 IN1 input line NO REL1 relay output NO IN2 IN2 input line CLK CLK output line GND Ground DTA DTA output line IN3 IN3 input line GND Ground IN4 IN4 input line A RS485 communication bus TML Built in feeder output 12VDC 0 2A B RS485 communication bus AUX Built in f...

Страница 5: ...CPR32 SE v3 0 User Manual Rev A doc 2017 04 14 5 15 Fig 2 Typical connection diagram for CPR32 SE v3 0 network controller ...

Страница 6: ...troller is designed for power supply from 230VAC 18VAC transformer with minimal power output 25VA but it can also be supplied with 12VDC The connection of power supply is shown in fig 4 and fig 5 If CPR is supplied with 18VAC then 12V backup battery can be connected in order to provide power supply in case of mains supply shortage The CPR charges backup battery with 300mA stabilized current up to ...

Страница 7: ...CPR32 SE v3 0 User Manual Rev A doc 2017 04 14 7 15 Fig 4 CPR32 SE v3 0 and PR402DR PR411DR controllers supplied with 18VAC Fig 5 CPR32 SE v3 0 and PRxx1 PRxx2 series controllers supplied with 12VDC ...

Страница 8: ...stors terminators connected at the ends of transmitting lines are not required In most cases communication works with any cable type standard telephone cable shielded or unshielded twisted pair etc but the recommended cable is unshielded twisted pair U UTP cat 5 Shielded cables should be limited to installations subject to strong electromagnetic interferences The RS485 communication standard used ...

Страница 9: ...unication bus including connected access controllers CPR32 SE network controller and communication interface e g UT 2USB the installer can proceed with installation and configuration of PR Master software At first it is necessary to configure subsystem selecting the option Networks in the main window of PR Master software and then the button Add In the newly opened window shown in fig 6 select the...

Страница 10: ... the CPR off and on Menu Settings Inputs Outputs In the window opened by means of this option it is possible to assign functions to CPR32 SE inputs and outputs Additionally in case of inputs the administrator can define their NO NC type and in case of outputs their normal inverted type All input functions can be divided into ON OFF monitored and ON monitored In case of ON OFF monitored input funct...

Страница 11: ...ivated at all controllers doors within subsystem network 12 Clear all alarms in subsystem ON monitored When the input is activated then all alarms in CPR32 NET and controllers within particular subsystem network are cleared The function 12 operates as a sum of 01 and 13 functions 13 Clear alarms in all controllers ON monitored When the input is activated then all alarms in controllers within parti...

Страница 12: ...of PR series controllers within the subsystem network 73 Alarm in CPR The output is activated for 3 minutes if Tamper Alarm or Power supply alarm is raised The function 67 operates as a sum of 81 and 82 functions 74 Low battery The output remains activated as long as charge level of backup battery connected to CPR32 NET unit is low 75 18VAC supply lost The output is activated after 15 minutes of 1...

Страница 13: ... output is activated for 3 minutes when the event memory buffer is filled in 75 90 Low battery 3 min The output remains activated for 3 minutes if charge level of backup battery connected to CPR32 NET unit is low 91 18VAC supply lost 3 min The output is activated for 3 minutes after 15 minutes of 18VAC power supply shortage to CPR32 NET unit 92 Battery failure 3 min The output is activated for 3 m...

Страница 14: ...tem is equipped with CPR32 SE network controller connected to PC through such serial interfaces as UT 2USB RUD 1 or UT 4 with virtual serial port then CPR is erroneously detected by Windows as Microsoft Serial Ball Point device In such case mouse cursor goes crazy erratically jumps around screen and PR Master software reports serial port error Note The problem which is described above is not cause...

Страница 15: ...ay have a negative impact on the environment and health The user is obliged to deliver equipment to the designated collection points of electric and electronic waste For detailed information on recycling contact your local authorities waste disposal company or point of purchase Separate collection and recycling of this type of waste contributes to the protection of the natural resources and is saf...

Отзывы: