Page 24 of 80
MCP Delay Line (Version 6.2.90.5)
Figure 2.30: The ATR19 module
The
ATR19
can also be operated as a non-symmetric (single input) amplifier with 50
Ω
impedance to ground, inverting (-) or
non-inverting (+). The non-symmetric operation is the default mode for the use of a delay-line detector in combination with
the
FT12(16)-TP
feedthrough and decoupling plugs.
The outputs of the
ATR19
allow verification of the signals after the first amplification stage on the
DLATR
board (“analog”
signal) and of the NIM or ECL timing output signals. Amplification, trigger threshold and timing signal width can be adjusted
by potentiometers (default) or externally by DC levels (0 to +5V), the CFD “walk” adjust is automated (push-button). The
double-hit dead-time of the CFD-outputs is about 20ns, depending on the input signal width.
Since the amplifier inputs are internally not tolerant to both signal polarities (no bipolar amplification), it is required to feed
signals into the inputs of corresponding polarity. Therefore positive input signals (e.g. the signal from the MCP) must be
connected via the inverting (-) input and negative signals have to be connected via the non-inverting (+) input. To ensure a
proper 50
Ω
termination of single polarity signals the other side of the internal amplifier input must be terminated to ground
(see chapter 2.6.1).
The recommended readout version of the
RoentDek
delay-line detectors involves the
FT12(16)-TP
plug with internal
signal transformers for the delay-line signals.
When the
ATR19
is delivered, channel 1 and 2 are by default prepared for positive input polarity (inverting) and the other
channels (used for the delay-line signals) for negative (non-inverting) signal polarity. If the voltages to the detector are
supplied in the recommended way the signal from the MCP front or back contact (positive) has to be connected to ch1- or
ch2- and the delay-line signals to ch3+ to ch6+ (or ch8+). Changing these settings requires to open the
ATR19
module (see
chapter 2.6.5).
2.6.1
Signal inputs and amplification
The
ATR19
hosts 3 or 4
DLATR
boards. Each board has two independent channels for amplification and timing
discrimination. Each differential amplifying stage has 100
Ω
impedance (2x50
Ω
to ground) and a selectable differential
amplification gain between 20 and 100. The gain can be adjusted by a potentiometer (“poti”) on each board and channel
independently through holes in the top lid of the
ATR19
module.
Содержание DLD120
Страница 6: ...Page 6 of 80 MCP Delay Line Version 6 2 90 5 ...
Страница 32: ...Page 32 of 80 MCP Delay Line Version 6 2 90 5 ...
Страница 51: ...MCP Delay Line Version 6 2 90 5 Page 51 of 80 Figure 4 4 BIASET2 Crate with four HV1 4 ...
Страница 68: ...Page 68 of 80 MCP Delay Line Version 6 2 90 5 ...
Страница 78: ...Page 78 of 80 MCP Delay Line Version 6 2 90 5 ...