background image

Installing the separator 10768

The digital and the DC-section of your layout must be strictly separated from each other. In order to be

sure that it is insulated separate the sections by using the ROCO plastic connectors 42611 on both sides

of the track or cut both track profiles (see fig. 6 on page 38).

In spite of the insulation the two sections are connected by the wheels of a train that passes from one

section to the other. This causes a short circuit between the digital and the conventional system that

could damage the digital amplifier or booster. In order to avoid the short circuit the separator is installed

between the DC transformer and the feeding track of the conventional section. The separator cuts the

connection between the DC transformer and the tracks automatically if the insulation between the two

sections is bridged by a train. So the short circuit detection of the Lokmaus®2 is not activated and the

train can pass from one system to the other.

Passing from the digital system to the DC-section the loco decoder automatically detects the different

feeding and assimilates the speed of the loco to the DC tension on the tracks. It also checks the polarity

of the tracks. If it matches the sense of driving of the loco then it continuos its run. If it doesn’t match the

train stops with the programmed deceleration delay. To make it continue, you have to set the knob of the

DC transformer to the middle (stop-position) and re-start the train.

In the same way the decoder reacts passing from the DC-section to the digital system. In the digital sec-

tion it immediately gets the digital information and regards these commands. It also checks the informa-

tion of the direction and in case that it doesn’t match the train stops with the programmed deceleration

delay. Now you must change the sense of driving of the train to make it re-start.

A pass-over-section

This simple wiring and procedure with the ROCO separator 10768 includes a small disadvantage if the-

re are several trains on the tracks:

Meanwhile one train passes the separation between the two systems the complete DC-section is fed by

the digital system. This causes all conventional locos to stop and all digital locos get digital informations

and could react according to those commands. This effect can be avoided by installing a

pass-over-section as shown in fig. 7 on page 38. This section must be longer than the longest train that

passes over it. It is insulated on both ends on both sides. A train that passes over this section only con-

nects the pass-over-section to the digital or to the DC system that is controlled by the separator. In that

way no digital information can enter the DC-section and influence the locos running there.

Turning loops in a digital layout

Everybody knows the problems caused by a turning loop in a conventional DC layout. Also on a digital

layout after a loop the left and the right track profile meet each other and would cause a short circuit if

you don’t install a wiring that avoids this matter.

The ROCO digital turnaround loop module 10769 solves the problems of a turnaround loop in the digital

system. Separate the turnaround loop at both ends on both track profiles as shown in fig. 5 on page 37.

The separated section must be longer than the longest train that will pass the loop. The feeding of the

turnaround loop is controlled by the turnaround loop module 10769. The modul itself is powered from a

track outside of the loop or directly connected to the amplifier or a booster.

The turnaround loop module 10769 works as follows: If a train enters the turnaround loop – doesn’t mat-

ter from which direction – and the polarity of the tracks before and inside the loop are not identical then a

short circuit occurs inside the turnaround loop modul that is detected immediately and the modul inverts

the polarity of the loops. This happens that fast that the amplifier doesn’t detect a short circuit or that the

train slows down. Now the loop has the right polarity to enter the loop.

This procedure must be repeated when the train leaves the loop, because now the polarity of the loop is

wrong for leaving it. For the digital operation of the trains the polarity of the tracks doesn’t matter the train

is not disturbed if the polarity of the tracks is inverted. It can pass the loop without stopping and with any

action that would have to be done by you.

To make sure that the turnaround modul 10769 detects the short circuit fast enough you must adjust the

sensitivity of the modul by the lateral potentiometer (see instruction of the modul).

30

Содержание LOKMAUS 2

Страница 1: ...Programming the Digital Turnout Drive 42624 26 Short Circuit and Overload 26 The Booster 10762 26 Using one or more Boosters 10762 26 Analogue Locos Locos without Digital Decoder on Digital Tracks 27 Compatibility of the new System RocoNet to the old Digital System Maus Bus 27 Compatibility of Control Devices and Decoders 27 The Menu System of the Lokmaus 2 28 Combination of Digital and Non Digita...

Страница 2: ...the loco q two digits LED display of the selected address or other information q 14 28 and 128 speed steps mode for all locos together or individually selectable for any loco sepa rately q emergency stop that stops the complete layout and cuts current supply q autoconfiguration of the RocoNet address q the system koordinates 31 devices such as the ROCO Lokmaus 2 the switch keyboard etc q setup men...

Страница 3: ...manufacturers may not have an autoconfiguration of the RocoNet address So you have to set the address by a setup procedure How this is done please read the instruction of those devi ces or contact the manufacturer If it is necessary to have an adaptor plug please take a look at www roco co at digital if there is a plug offered by ROCO ATTENTION If you make your own adaptor plug you must strictly a...

Страница 4: ...a digitally controlled smoke generator di gital uncoupler sound etc Therefore on most of the locos the function keys don t control nothing To operate those additional functions the loco must be equipped with a special deoder or an additional function decoder For the future it is ROCO s plan to raise the playworth of the railroad by adding functions to locos and cars So these functions already have...

Страница 5: ... that means e g all locos run with 28 speed steps The second defines the speed steps different for each loco e g loco 04 runs with 28 speed step loco 17 with 128 and loco 98 only with 14 The factory default setting is 28 speed steps for all locomotives this setting is restored by the system reset using C7 This setup is done by the menu C6 see page 29 You can define the ge neral mode to 14 speed st...

Страница 6: ...arameters of a loco such as the address minimum speed acceleration and deceleration delay and the maximum speed Pressing P and one of the functi on buttons star or F1 to F4 leads you into the standard programming mode By the same procedure you select the parameter that you want to program see the list below Meanwhile you press the two buttons the display shows SP and all trains on the layout stop ...

Страница 7: ...s to develop a device that is more powerful and supports to read the decoder If you use the Lokmaus 2 together with a LZ100 and LV101 by Lenz then you can read out the loco decoder already today If you select F4 to write the decoder then you must indicate the value you want to program by the but tons up and down By principle all values from 00 to 99 are programmable but most of the decoders only s...

Страница 8: ...cedure the Lokmaus 2 automatically return to the normal operation Release the green programming wire from the track The turnout drive now can be operated by the button F1 During this programming procedure further digital turnout drives 42624 may stay installed because the turnout drive takes the address only in case that the green programming wire is attached to the track Be careful with switch de...

Страница 9: ...racks The second generation of the ROCO digital system does not support controlling a loco without a digital decoder also the old digital is cool system didn t The reason is that a loco without digital decoder on a digital layout causes an enormeously bothering high frequency noise There is also the danger that small motors originally N scale motors that are installed in some small H0 locos could ...

Страница 10: ...hile you re plug the Lokmaus 2 The display shows you the first menu C0 Using the buttons up and down you can also select other menus e g C3 Push P again and the display shows the actual value of C3 By the buttons up and down you can change this value of C3 and pushing P you confirm and activate your input Pushing STOP you quit this menu The following list tells you the various menus and explains t...

Страница 11: ...the values for C9 and the programming methods you select by this values C9 AO RG CV PM C9 AO RG CV PM 00 08 on 01 on 09 on on 02 on 10 on on 03 on on 11 on on on 04 on 12 on on 05 on on 13 on on on 06 on on default 14 on on on 07 on on on 15 on on on on AO address only RG register mode CV CV direkt PM paged mode Default is 14 at the Lokmaus 2 that are included in the starting sets 41203 and 41212 ...

Страница 12: ...nd all digital locos get digital informations and could react according to those commands This effect can be avoided by installing a pass over section as shown in fig 7 on page 38 This section must be longer than the longest train that passes over it It is insulated on both ends on both sides A train that passes over this section only con nects the pass over section to the digital or to the DC sys...

Страница 13: ...co is the programming of the CV29 must be corrected to change the inversed sense of driving How to program the CV29 you read on page 25 headlights of the pilot car e g By programming the CV29 you must change the sense of driving of the ICE don t match direction of the pilot car Put the pilot car without loco on the programming track How to program the CV29 you read on page 25 the speed step mode c...

Страница 14: ...you have disabled the au toconfiguration you must correct the device address yourself How to change the device address you can read on page 28 error code E7 The actual RocoNet address of the Lokmaus 2 is not addressed This error message may occur because you added more devices to the system than defined in the menu C8 How you raise the number of devices you read on page 29 This error message can a...

Страница 15: ...ok ok ok Lenz LE100 ok ok LE111N ok ok ok ok LE131N ok ok ok ok MRC AC310 ok Soundtraxx DSD150 ok ok System One CH155 ok ok ok Zimo MX61R N ok ok ok ok Devices of other brands as input devices at the RocoNet manufacturer device autoconfiguration comment Lenz LH100 you need an adaptor plug LH200 ok can t be master LI100 you need an adaptor plug Arnold 81210 you need an adaptor plug 81220 you need a...

Страница 16: ... 10740 see page 25 10741 only 14 speed steps Proprietes du décodeur ROCO LENZ Lokdecoder CV valeurs paramêtre limitations 01 01 99 adresse de la locomotive pas pour l ICE 215 de 41100 02 01 15 vitesse minimale pas pour le décodeur 10740 03 01 31 vitesse de accelération pas pour le décodeur 10740 04 01 31 vitesse de décélération pas pour le décodeur 10740 05 01 15 vitesse maximale seulement ROCO 10...

Отзывы: