Chapter
3
Access Procedures
!
ATTENTION:
To avoid an electric shock hazard, ensure that all
power to the drive has been removed before performing the
following.
!
ATTENTION:
To avoid an electric shock hazard, verify that the
voltage on the bus capacitors has discharged completely before
servicing. Check the DC bus voltage at the Power Terminal
Block by measuring between the +DC and -DC terminals,
between the +DC terminal and the chassis, and between the -DC
terminal and the chassis. The voltage must be zero for all three
measurements.
!
ATTENTION:
The sheet metal cover and mounting screws on
the ASIC Board located on the power structure are energized at
(-) DC bus potential high voltage. Risk of electrical shock,
injury, or death exists if someone comes into contact with the
assembly.
!
ATTENTION:
HOT surfaces can cause severe burns.
Do not
touch the heatsink surface during operation of the drive. After
disconnecting power allow time for cooling.
!
ATTENTION:
Hazard of permanent eye damage exists when
using optical transmission equipment. This product emits intense
light and invisible radiation. Do not look into fiber-optic ports or
fiber-optic cable connectors.
!
ATTENTION:
This drive contains
ESD
(Electrostatic
Discharge) sensitive parts and assemblies. Static control
precautions are required when installing, testing, servicing or
repairing this assembly. Component damage may result if ESD
control procedures are not followed. If you are not familiar with
static control procedures, reference A-B publication 8000-4.5.2,
“Guarding Against Electrostatic Damage” or any other
applicable ESD protection handbook.
Содержание powerflex 700h
Страница 4: ...soc ii Summary of Changes Notes ...
Страница 8: ...4 ...
Страница 46: ...2 14 Component Test Procedures ...
Страница 92: ...3 46 Access Procedures Notes ...
Страница 98: ...A 2 Service Tools and Equipment Notes ...
Страница 106: ...B 8 Schematics Notes ...
Страница 116: ...C 10 Disassembly Assembly Diagrams Notes ...
Страница 119: ......